FireCADCalc

H₂S Odour Scrubber: Hypochlorite, Caustic and Water Use

Hydrogen sulphide removed from an air stream, sodium hypochlorite and caustic consumed by stoichiometry, scrubbing water flow and caustic solution volume.

Refinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Pumping station 120 m3/min, 50 ppmv, 25 CHeadworks 400 m3/min, 5 ppmv, 15 C

Accepted: 0.06 to 6,000 m³/min
Accepted: 0.01 to 10,000
Accepted: -10 to 60 °C
Accepted: 0.78954 to 1.0856 atm
Accepted: 0.8 to 1.5 kg/m³
Accepted: 0.5 to 5
Accepted: 1,000 to 1,600 kg/m³
Accepted: 5 to 75 %

Results

Stoichiometry of H₂S + 4 NaOCl + 2 NaOH → Na₂SO₄ + 4 NaCl + 2 H₂O: 8.74 kg of hypochlorite and 2.35 kg of caustic per kg of H₂S. Practical scrubbers use 2-3 kg NaOH per kg of sulphide and a pH of 11-12.5; the supplier fixes the water rate.

H₂S concentration7.2066mg/m³
H₂S to treat4.1510kg/d
Sodium hypochlorite (8.74 kg/kg)36.268kg/d
Caustic (2.35 kg/kg)9.7442kg/d
Caustic solution volume12.821L/d
Scrubbing water0.72240m³/min

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Pumping station 120 m3/min, 50 ppmv, 25 C. The inputs, in the units selected above:

InputValue
Air flow120.00 m³/min
H₂S in the air (ppmv)50.000 -
Air temperature25.000 °C
Air pressure1.0000 atm
Air density1.2040 kg/m³
Liquid-to-gas mass ratio2.0000 -
Caustic solution density1,520.0 kg/m³
NaOH in the solution50.000 %

Applying the formula below gives:

ResultValue
H₂S concentration69.649 mg/m³
H₂S to treat12.035 kg/d
Sodium hypochlorite (8.74 kg/kg)105.15 kg/d
Caustic (2.35 kg/kg)28.252 kg/d
Caustic solution volume37.174 L/d
Scrubbing water0.28896 m³/min

Open this example in the calculator and change any input.

Formula

\(C_{H_2S} = y\frac{pM_{H_2S}}{RT}, \quad M_{NaOCl} = \frac{4M_{NaOCl}}{M_{H_2S}}M_{H_2S}, \quad M_{NaOH} = \frac{2M_{NaOH}}{M_{H_2S}}M_{H_2S}\)

Variables

Symbol Meaning SI unit
\(Q_a\) Air flow m³/s
\(y\) H₂S in the air (ppmv) -
\(T\) Air temperature K
\(p\) Air pressure Pa
\(\rho_a\) Air density kg/m³
\(L/G\) Liquid-to-gas mass ratio -
\(\rho_s\) Caustic solution density kg/m³
\(w\) NaOH in the solution -
\(C_{H_2S}\) H₂S concentration kg/m³
\(M_{H_2S}\) H₂S to treat kg/s
\(M_{NaOCl}\) Sodium hypochlorite (8.74 kg/kg) kg/s
\(M_{NaOH}\) Caustic (2.35 kg/kg) kg/s
\(V_{NaOH}\) Caustic solution volume m³/s
\(Q_w\) Scrubbing water m³/s

Method and standards

Stoichiometric chemical scrubber requirements.

Where it is used

  • Odour control at pumping stations and headworks.
  • Chemical storage sizing.

Common mistakes

  • Using ppm by mass.
  • Ignoring caustic make-up.

Assumptions and limits

  • Complete oxidation to sulphate; real consumption is higher.

Questions and answers

Is the caustic always needed?

It replaces the alkalinity the reaction consumes; if the scrubbing water has enough alkalinity, less or none is added.

What do the defaults represent?

An illustrative case: Pumping station 120 m3/min, 50 ppmv, 25 C. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Metcalf and Eddy (Tchobanoglous, Stensel, Tsuchihashi and Burton), Wastewater Engineering: Treatment and Resource Recovery, 5th ed. (McGraw-Hill, 2014), sec. 16-3, eq. 16-3, Table 16-9 and Example 16-1

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.