Fluid Outlet Temperature in a Tube at Constant Wall Temperature

Film coefficient by Sieder–Tate and the outlet temperature, duty and log-mean difference for a fluid heated or cooled in a tube at constant wall temperature.

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Laminar heavy oil 0.05 kg/s in 20 mm x 6 m, steam at 150 CWater cooled in a 25 mm tube 10 m long by a 15 C wall, 0.3 kg/s from 70 C

Accepted: 2 to 500 mm
Accepted: 0.1 to 100 m
Accepted: 0.036 to 360,000 kg/h
Accepted: 0.5 to 6 kJ/(kg·K)
Accepted: 0.001 to 10,000 mPa·s
Accepted: 0.01 to 2 W/(m·K)
Accepted: 0.01 to 100
Accepted: -73.15 to 626.85 °C
Accepted: -73.15 to 626.85 °C

Results

Turbulent Sieder–Tate: Nu = 0.027 Re^0.8 Pr^1/3 (μ/μ_w)^0.14.

Reynolds number23,506
Prandtl number4.2453
Film coefficient3,462.9W/(m²·K)
hπDL/(ṁc_p)2.1689
Outlet temperature21.287°C
Heat transferred-61.086kW
Log-mean temperature difference-22.460K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Laminar heavy oil 0.05 kg/s in 20 mm x 6 m, steam at 150 C. The inputs, in the units selected above:

InputValue
Tube inside diameter20.000 mm
Tube length6.0000 m
Flow180.00 kg/h
Specific heat2.0000 kJ/(kg·K)
Viscosity at the bulk temperature50.000 mPa·s
Thermal conductivity0.13000 W/(m·K)
Viscosity ratio bulk to wall (1 if unknown)0.40000 -
Inlet temperature40.000 °C
Wall temperature150.00 °C

Applying the formula below gives:

ResultValue
Reynolds number63.662
Prandtl number769.23
Film coefficient58.119 W/(m²·K)
hπDL/(ṁc_p)0.21910
Outlet temperature61.644 °C
Heat transferred2.1644 kW
Log-mean temperature difference98.783 K

Open this example in the calculator and change any input.

Formula

\(Nu = 0.027Re^{0.8}Pr^{1/3}\left(\frac{\mu}{\mu_w}\right)^{0.14}\ (\text{turbulent}), \quad Nu = 1.86\left(\frac{RePrD}{L}\right)^{1/3}\left(\frac{\mu}{\mu_w}\right)^{0.14}\ (\text{laminar})\)

\(T_2 = T_w - (T_w - T_1)\exp\left(-\frac{h\pi DL}{\dot mc_p}\right)\)

Variables

Symbol Meaning SI unit
\(D\) Tube inside diameter m
\(L\) Tube length m
\(\dot m\) Flow kg/s
\(c_p\) Specific heat J/(kg·K)
\(\mu\) Viscosity at the bulk temperature Pa·s
\(k\) Thermal conductivity W/(m·K)
\(\mu/\mu_w\) Viscosity ratio bulk to wall (1 if unknown) -
\(T_1\) Inlet temperature K
\(T_w\) Wall temperature K
\(Re\) Reynolds number -
\(Pr\) Prandtl number -
\(h\) Film coefficient W/(m²·K)
\(NTU\) hπDL/(ṁc_p) -
\(T_2\) Outlet temperature K
\(Q\) Heat transferred W
\(\Delta T_{lm}\) Log-mean temperature difference K

Method and standards

Energy balance of a tube with a uniform wall temperature.

Where it is used

  • Steam-traced or jacketed line heaters.
  • Condensing-steam tube heaters.

Common mistakes

  • Using the arithmetic mean temperature difference.
  • Applying the turbulent equation in transition flow.

Assumptions and limits

  • Constant properties and wall temperature.

Questions and answers

Why is no iteration needed?

With constant properties and a constant wall temperature the bulk temperature approaches the wall exponentially: T₂ = T_w − (T_w − T₁)e^(−NTU). Designers show the trial-and-error route reaching the same answer.

What is the viscosity ratio for?

Viscous oils heated at the wall flow more easily near it, raising h; cooling has the opposite effect.

What do the defaults represent?

An illustrative case: Laminar heavy oil 0.05 kg/s in 20 mm x 6 m, steam at 150 C. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Serth, Process Heat Transfer: Principles and Applications (Academic Press, 2007), sec. 2.5, Example 2.6 (Sieder and Tate, 1936)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.