Worked example
Example: District heating 200 mm pipe, 1.2 m deep, 80 C, 5 C surface, 60 mm PUR (0.027), soil 1.5. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pipe outside diameter (bare) | 219.00 mm |
| Depth of the pipe centre below the surface | 1.2000 m |
| Soil thermal conductivity | 1.5000 W/(m·K) |
| Pipe outer wall temperature | 80.000 °C |
| Ground surface temperature | 5.0000 °C |
| Insulation thickness (0 = bare) | 60.000 mm |
| Insulation conductivity | 0.027000 W/(m·K) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Shape factor per metre | 2.3752 |
| Soil resistance per metre | 0.28068 |
| Insulation resistance per metre | 2.5755 |
| Heat loss per metre of pipe | 26.259 W/m |
Open this example in the calculator and change any input.
Formula
\(S = \frac{2\pi L}{\cosh^{-1}(2z/D)}, \quad q' = \frac{T_p - T_s}{\frac{1}{k_eS/L} + \frac{\ln(D_{ins}/D)}{2\pi k_{ins}}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D\) | Pipe outside diameter (bare) | m |
| \(z\) | Depth of the pipe centre below the surface | m |
| \(k_e\) | Soil thermal conductivity | W/(m·K) |
| \(T_p\) | Pipe outer wall temperature | K |
| \(T_s\) | Ground surface temperature | K |
| \(t_{ins}\) | Insulation thickness (0 = bare) | m |
| \(k_{ins}\) | Insulation conductivity | W/(m·K) |
| \(S/L\) | Shape factor per metre | - |
| \(R_e\) | Soil resistance per metre | - |
| \(R_{ins}\) | Insulation resistance per metre | - |
| \(q'\) | Heat loss per metre of pipe | W/m |
Method and standards
Conduction shape factor for a buried cylinder in series with insulation.
Where it is used
- District heating and oil pipeline losses.
- Freeze protection of buried water lines.
Common mistakes
- Measuring depth to the top of the pipe instead of its centre.
- Using the soil temperature at depth as the surface temperature.
Assumptions and limits
- Steady state, uniform soil, long pipe.
Questions and answers
What surface temperature should I use?
The ground surface temperature, close to the air temperature averaged over days; in winter it can be well below the soil temperature at pipe depth.
Does depth matter much?
Only logarithmically: doubling the depth cuts the loss by perhaps 20–30 %.
What do the defaults represent?
An illustrative case: District heating 200 mm pipe, 1.2 m deep, 80 C, 5 C surface, 60 mm PUR (0.027), soil 1.5. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Serth, Process Heat Transfer: Principles and Applications (Academic Press, 2007), sec. 1.7, Table 1.3, Examples 1.8 and 1.9