Asymptotic Fouling Resistance with Time (Kern–Seaton Model)

Fouling resistance growth toward its asymptotic value, the time to reach a chosen fraction, and the fouled overall coefficient after a running time.

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Cooling water fouling, R_inf 0.0003, tau 2,000 h, 6 monthsCrude preheat train, R_inf 0.002, tau 1,200 h, 1 year, U_c 450

Accepted: 1E-6 to 0.01 m²·K/W
Accepted: 1 to 83,333 h
Accepted: 0 to 83,333 h
Accepted: 1 to 100,000 W/(m²·K)
Accepted: 1 to 99.9 %

Results

Deposition at a constant rate with removal proportional to the deposit (Kern and Seaton; Taborek et al.) gives R_f = R_f,∞(1 − e^(−t/τ_c)). Fit R_f,∞ and τ_c from plant U-versus-time data; there is often an induction period before fouling starts.

Fouling resistance after the running time2.6642e-04m²·K/W
Share of the asymptote reached88.808%
Fouled overall coefficient1,071.7W/(m²·K)
Loss of overall coefficient28.553%
Time to reach the chosen fraction5,991.5h
Fully fouled overall coefficient1,034.5W/(m²·K)

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Cooling water fouling, R_inf 0.0003, tau 2,000 h, 6 months. The inputs, in the units selected above:

InputValue
Asymptotic fouling resistance3.0000e-04 m²·K/W
Time constant (time to 63 % of the asymptote)2,000.0 h
Running time4,380.0 h
Clean overall coefficient1,500.0 W/(m²·K)
Fraction of the asymptote for the time question95.000 %

Applying the formula below gives:

ResultValue
Fouling resistance after the running time2.6642e-04 m²·K/W
Share of the asymptote reached88.808 %
Fouled overall coefficient1,071.7 W/(m²·K)
Loss of overall coefficient28.553 %
Time to reach the chosen fraction5,991.5 h
Fully fouled overall coefficient1,034.5 W/(m²·K)

Open this example in the calculator and change any input.

Formula

\(R_f(t) = R_{f,\infty}\left(1 - e^{-t/\tau_c}\right), \quad t_f = -\tau_c\ln(1 - f), \quad \frac{1}{U_f} = \frac{1}{U_c} + R_f\)

Variables

Symbol Meaning SI unit
\(R_{f,\infty}\) Asymptotic fouling resistance m²·K/W
\(\tau_c\) Time constant (time to 63 % of the asymptote) s
\(t\) Running time s
\(U_c\) Clean overall coefficient W/(m²·K)
\(f\) Fraction of the asymptote for the time question -
\(R_f(t)\) Fouling resistance after the running time m²·K/W
\(R_f/R_{f,\infty}\) Share of the asymptote reached -
\(U_f(t)\) Fouled overall coefficient W/(m²·K)
\(1 - U_f/U_c\) Loss of overall coefficient -
\(t_f\) Time to reach the chosen fraction s
\(U_{f,\infty}\) Fully fouled overall coefficient W/(m²·K)

Method and standards

Asymptotic deposition–removal fouling model.

Where it is used

  • Predicting exchanger performance between cleanings.
  • Choosing a fouling allowance from operating data.

Common mistakes

  • Designing on the full asymptotic resistance when cleaning is frequent.
  • Assuming all fouling is asymptotic.

Assumptions and limits

  • Constant operating conditions; no induction period.

Questions and answers

What does the time constant mean?

After one time constant the resistance reaches 63 % of its final value, after three about 95 %.

Which fouling follows this curve?

Particulate and some crystallisation fouling where the deposit erodes as it grows; chemical-reaction and corrosion fouling often grow linearly instead.

What do the defaults represent?

An illustrative case: Cooling water fouling, R_inf 0.0003, tau 2,000 h, 6 months. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Shah and Sekulić, Fundamentals of Heat Exchanger Design (Wiley, 2003), sec. 13.2.6, eqs. 13.11 to 13.13 and Example 13.1 (Kern and Seaton, 1959; Taborek et al., 1972)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.