FireCADCalc

Wet Bulb Globe Temperature (WBGT) for Heat Stress

Wet bulb globe temperature indoors or outdoors in sunshine from the natural wet-bulb, globe and air temperatures, the index used to screen heat stress at work.

Inputs

Examples: Illustrative hot workshop: 26 / 40 / 33 C indoorsOutdoor construction site in sun: 25 / 50 / 34 CBoiler house: 28 / 45 / 38 C

Accepted: -10 to 60 °C
Accepted: -10 to 100 °C
Accepted: -10 to 60 °C

Results

Yaglou–Minard WBGT (weights 0.7/0.3 indoors, 0.7/0.2/0.1 in sun). Compare with the reference values for the work rate and acclimatisation in the occupational guidance that applies; use a 150 mm black globe and an unshielded, naturally ventilated wet bulb.

Wet bulb globe temperature30.200°C
Indoor formula 0.7t_nw + 0.3t_g30.200°C
Outdoor formula 0.7t_nw + 0.2t_g + 0.1t_a29.500°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative hot workshop: 26 / 40 / 33 C indoors. The inputs, in the units selected above:

InputValue
ExposureIndoors or outdoors without sun
Natural wet-bulb temperature26.000 °C
Black globe temperature40.000 °C
Air (dry-bulb) temperature33.000 °C

Applying the formula below gives:

ResultValue
Wet bulb globe temperature30.200 °C
Indoor formula 0.7t_nw + 0.3t_g30.200 °C
Outdoor formula 0.7t_nw + 0.2t_g + 0.1t_a29.500 °C

Open this example in the calculator and change any input.

Formula

\(WBGT_{in} = 0.7t_{nw} + 0.3t_g, \quad WBGT_{out} = 0.7t_{nw} + 0.2t_g + 0.1t_a\)

Variables

Symbol Meaning SI unit
\(\text{location}\) Exposure -
\(t_{nw}\) Natural wet-bulb temperature K
\(t_g\) Black globe temperature K
\(t_a\) Air (dry-bulb) temperature K
\(WBGT\) Wet bulb globe temperature K
\(WBGT_{in}\) Indoor formula 0.7t_nw + 0.3t_g K
\(WBGT_{out}\) Outdoor formula 0.7t_nw + 0.2t_g + 0.1t_a K

Method and standards

WBGT heat-stress index.

Where it is used

  • Foundries, boiler houses, kitchens and outdoor work.
  • Sports and military training heat management.

Common mistakes

  • Using the psychrometric (aspirated) wet bulb instead of the natural wet bulb.
  • Using the indoor formula in direct sun.

Assumptions and limits

  • Instruments to the usual specification (150 mm black globe, natural wet bulb).

References

  • Wet bulb globe temperature index

Questions and answers

Why does the wet bulb carry 70 % of the weight?

Sweat evaporation is the body's main cooling route in heat; the natural wet bulb reflects humidity, wind and radiation on a wetted surface.

Is WBGT the same as the heat index?

No: the heat index uses air temperature and humidity in shade; WBGT also counts radiant heat and wind, so it suits work in sun and near hot plant.

What do the defaults represent?

An illustrative hot workshop: natural wet bulb 26 °C, globe 40 °C and air 33 °C, indoors.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Yaglou and Minard, Control of heat casualties at military training centers, AMA Arch. Ind. Health 16 (1957) 302–316, Parsons, Human Thermal Environments, 3rd ed. (CRC Press, 2014), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.