Worked example
Example: Illustrative 400 m3 house, 1500 m3/h at 50 Pa. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Leakage flow at 50 Pa | 1,500.0 m³/h |
| Building internal volume | 400.00 m³ |
| Envelope area | 330.00 m² |
| Flow exponent | 0.65000 - |
| ACH50 to natural ACH divisor | 20.000 - |
| Air density | 1.2000 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Air changes at 50 Pa | 3.7500 1/h |
| Air permeability | 4.5455 m³/(h·m²) |
| Estimated natural air change rate | 0.18750 1/h |
| Leakage at 4 Pa | 290.47 m³/h |
| Equivalent leakage area at 4 Pa | 312.49 cm² |
Open this example in the calculator and change any input.
Formula
\(n_{50} = \frac{\dot V_{50}}{V}, \quad \dot V_4 = \dot V_{50}\left(\frac{4}{50}\right)^n, \quad ELA = \dot V_4\sqrt{\frac{\rho}{2\cdot4\,\mathrm{Pa}}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_{50}\) | Leakage flow at 50 Pa | m³/s |
| \(V\) | Building internal volume | m³ |
| \(A_E\) | Envelope area | m² |
| \(n\) | Flow exponent | - |
| \(N\) | ACH50 to natural ACH divisor | - |
| \(\rho\) | Air density | kg/m³ |
| \(n_{50}\) | Air changes at 50 Pa | 1/s |
| \(q_{50}\) | Air permeability | m/s |
| \(n_{nat}\) | Estimated natural air change rate | 1/s |
| \(\dot V_4\) | Leakage at 4 Pa | m³/s |
| \(ELA_4\) | Equivalent leakage area at 4 Pa | m² |
Method and standards
Pressurisation test.
Where it is used
- Energy rating and building regulations checks.
- Ventilation design for tight houses.
Common mistakes
- Comparing ACH50 between very different building sizes.
- Treating ACH50 as natural infiltration.
Assumptions and limits
- Power-law leakage; single-zone building.
References
- Fan pressurisation test interpretation
- ASHRAE Handbook of Fundamentals (ASHRAE)
- ch. 16
Questions and answers
What ACH50 is good?
About 3 or below for new efficient homes, under 1 for very tight (Passivhaus-level 0.6) houses; old houses often exceed 10.
Is ACH50 the real infiltration?
No: it is measured at 50 Pa; natural infiltration is roughly ACH50 divided by 10–30.
What do the defaults represent?
An illustrative 400 m³ house leaking 1,500 m³/h at 50 Pa with 330 m² of envelope, flow exponent 0.65.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.