Worked example
Example: Illustrative plasterboard, wool, brick, no barrier. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Indoor temperature | 20.000 °C |
| Indoor relative humidity | 60.000 % |
| Outdoor temperature | -5.0000 °C |
| Outdoor relative humidity | 90.000 % |
| Inside surface resistance | 0.13000 m²·K/W |
| Outside surface resistance | 0.040000 m²·K/W |
| Layer 1 (inside) thickness | 12.500 mm |
| Layer 1 conductivity | 0.21000 W/(m·K) |
| Layer 1 vapour resistance factor | 10.000 - |
| Layer 2 thickness | 100.00 mm |
| Layer 2 conductivity | 0.040000 W/(m·K) |
| Layer 2 vapour resistance factor | 1.0000 - |
| Layer 3 (outside) thickness | 100.00 mm |
| Layer 3 conductivity | 0.77000 W/(m·K) |
| Layer 3 vapour resistance factor | 10.000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Thermal transmittance | 0.34972 W/(m²·K) |
| Inside surface temperature | 18.863 °C |
| Temperature at the layer 1–2 interface | 18.343 °C |
| Temperature at the layer 2–3 interface | -3.5148 °C |
| Outside surface temperature | -4.6503 °C |
| Smallest saturation margin (negative = condensation) | -756.34 Pa |
| Plane of smallest margin (1 inside surface … 4 outside surface) | 3.0000 |
Open this example in the calculator and change any input.
Formula
\(T_{j+1} = T_j - q\frac{d_j}{\lambda_j}, \quad p(s_d) = p_i - (p_i - p_o)\frac{s_d}{s_{d,tot}}, \quad s_d = \mu d\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_i\) | Indoor temperature | K |
| \(\varphi_i\) | Indoor relative humidity | - |
| \(T_o\) | Outdoor temperature | K |
| \(\varphi_o\) | Outdoor relative humidity | - |
| \(R_{si}\) | Inside surface resistance | m²·K/W |
| \(R_{so}\) | Outside surface resistance | m²·K/W |
| \(d_1\) | Layer 1 (inside) thickness | m |
| \(\lambda_1\) | Layer 1 conductivity | W/(m·K) |
| \(\mu_1\) | Layer 1 vapour resistance factor | - |
| \(d_2\) | Layer 2 thickness | m |
| \(\lambda_2\) | Layer 2 conductivity | W/(m·K) |
| \(\mu_2\) | Layer 2 vapour resistance factor | - |
| \(d_3\) | Layer 3 (outside) thickness | m |
| \(\lambda_3\) | Layer 3 conductivity | W/(m·K) |
| \(\mu_3\) | Layer 3 vapour resistance factor | - |
| \(U\) | Thermal transmittance | W/(m²·K) |
| \(T_{si}\) | Inside surface temperature | K |
| \(T_{12}\) | Temperature at the layer 1–2 interface | K |
| \(T_{23}\) | Temperature at the layer 2–3 interface | K |
| \(T_{so}\) | Outside surface temperature | K |
| \(\min(p_s - p)\) | Smallest saturation margin (negative = condensation) | Pa |
| \(k\) | Plane of smallest margin (1 inside surface … 4 outside surface) | - |
Method and standards
Glaser diagram.
Where it is used
- Wall and roof build-up design.
- Retrofit internal insulation checks.
Common mistakes
- Placing vapour-tight layers on the cold side.
- Treating the steady method as a moisture-content prediction.
Assumptions and limits
- Steady state; one-dimensional; no liquid transport.
References
- Glaser steady-state vapour diffusion method
Questions and answers
Why does insulation inside a masonry wall risk condensation?
The masonry outside the insulation is cold, but vapour passes easily through the insulation, so it reaches the cold layer above its dew point.
Where should the vapour barrier go?
On the warm side of the insulation, so the vapour pressure drops before the temperature does.
What do the defaults represent?
An illustrative 12.5 mm plasterboard, 100 mm mineral wool and 100 mm brick wall at 20 °C, 60 % inside and −5 °C, 90 % outside, with no vapour barrier.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Hagentoft, Introduction to Building Physics (Studentlitteratur, 2001)