FireCADCalc

Thermostat Setback Heating Savings

Heating energy saved by lowering the thermostat for part of each day, by the degree-hour method with an effectiveness factor for the building's cool-down lag.

Inputs

Examples: Illustrative 8 h, 5 K night setbackOffice weekend-style 14 h, 6 KSmall 2 K setback, mild climate

Accepted: 6.85 to 36.85 °C
Accepted: 0.1 to 20 K
Accepted: 0 to 24 h
Accepted: -53.15 to 26.85 °C
Accepted: 10 to 100 %
Accepted: 0 to 27,778,000 kWh

Results

Heat loss is roughly proportional to the inside–outside temperature difference, so lowering the setpoint by ΔT for h hours a day cuts the season's degree-hours by about ΔT·h/[24(T_i − T̄_o)]. The building cools gradually and must be reheated, so only part of the setback is realised; the effectiveness factor (about 0.5–0.8, lower for heavy buildings and heat pumps with electric backup) accounts for that. The often-quoted rule is about 1 % saving per °F of 8-hour setback.

Share of heating energy saved7.2917%
Annual energy saved1,093.8kWh
Degree-hours avoided per day40.000°C·h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 8 h, 5 K night setback. The inputs, in the units selected above:

InputValue
Normal setpoint21.000 °C
Setback5.0000 K
Setback hours per day8.0000 h
Mean outdoor temperature in the heating season5.0000 °C
Setback effectiveness (cool-down lag)70.000 %
Annual heating energy without setback15,000 kWh

Applying the formula below gives:

ResultValue
Share of heating energy saved7.2917 %
Annual energy saved1,093.7 kWh
Degree-hours avoided per day40.000 °C·h

Open this example in the calculator and change any input.

Formula

\(f = \varepsilon\frac{\Delta T\cdot h/24}{T_i - \bar T_o}, \quad \Delta E = fE\)

Variables

Symbol Meaning SI unit
\(T_i\) Normal setpoint K
\(\Delta T\) Setback K
\(h\) Setback hours per day s
\(\bar T_o\) Mean outdoor temperature in the heating season K
\(\varepsilon\) Setback effectiveness (cool-down lag) -
\(E\) Annual heating energy without setback J
\(f\) Share of heating energy saved -
\(\Delta E\) Annual energy saved J
\(\Delta T\cdot h\) Degree-hours avoided per day K·s

Method and standards

Setback savings.

Where it is used

  • Energy advice and controls retrofits.
  • Comparing schedules.

Common mistakes

  • Assuming the full setback is realised.
  • Using the design outdoor temperature as the seasonal mean.

Assumptions and limits

  • Heat loss proportional to temperature difference; constant internal gains.

References

  • Degree-hour estimate of setback savings

Questions and answers

Does reheating cancel the savings?

No: a cooler building loses less heat, which outweighs the recovery energy, but not all of the theoretical saving is realised.

Is setback wise with heat pumps?

Only with controls that avoid electric resistance backup during recovery.

What do the defaults represent?

An illustrative home at 21 °C with an 8-hour, 5 K night setback, 5 °C mean winter temperature and 15,000 kWh annual heating.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

McQuiston, Parker, Spitler and Taherian, Heating, Ventilating and Air Conditioning, and ASHRAE, Principles of Heating, Ventilating and Air Conditioning, 8th ed. (ASHRAE, 2017)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.