FireCADCalc

Infiltration from Leakage Area: Combined Stack and Wind

Air infiltration of a house from its effective leakage area with stack and wind coefficients (LBL model), the air change rate and the sensible heat loss.

Inputs

Examples: Illustrative one-storey houseTwo-storey leaky house, cold and windyTight house, calm

Accepted: 1 to 1,000,000
Accepted: 0 to 0.01
Accepted: 0 to 0.01
Accepted: -23.15 to 46.85 °C
Accepted: -53.15 to 56.85 °C
Accepted: 0 to 180 km/h
Accepted: 1 to 10,000,000 m³

Results

The Lawrence Berkeley Laboratory (Sherman–Grimsrud) model treats a house as one zone whose leaks have an effective area A_L measured by a blower-door test at 4 Pa. Stack and wind pressures add in quadrature: Q = A_L√(C_sΔT + C_wU²) with Q in L/s, A_L in cm², ΔT in K and U in m/s. C_s depends on the number of storeys (about 0.000145 for one, 0.000290 for two, 0.000435 for three) and C_w on height and shelter class; take both from the design guide. The heat loss uses outdoor air density and c_p = 1.006 kJ/kg·K.

Stack-only infiltration30.700L/s
Wind-only infiltration22.946L/s
Combined infiltration38.328L/s
Air changes per hour0.34495
Sensible heat loss1.3197kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative one-storey house. The inputs, in the units selected above:

InputValue
Effective leakage area at 4 Pa (cm²)500.00 -
Stack coefficient (L/s)²/(cm⁴·K)1.4500e-04 -
Wind coefficient (L/s)²/(cm⁴·(m/s)²)1.0400e-04 -
Indoor temperature21.000 °C
Outdoor temperature-5.0000 °C
Wind speed at the weather station16.200 km/h
Building volume400.00 m³

Applying the formula below gives:

ResultValue
Stack-only infiltration30.700 L/s
Wind-only infiltration22.946 L/s
Combined infiltration38.328 L/s
Air changes per hour0.34495
Sensible heat loss1.3197 kW

Open this example in the calculator and change any input.

Formula

\(Q = A_L\sqrt{C_s\Delta T + C_wU^2}, \quad ACH = \frac{3600\,Q}{V}\)

Variables

Symbol Meaning SI unit
\(A_L\) Effective leakage area at 4 Pa (cm²) -
\(C_s\) Stack coefficient (L/s)²/(cm⁴·K) -
\(C_w\) Wind coefficient (L/s)²/(cm⁴·(m/s)²) -
\(T_i\) Indoor temperature K
\(T_o\) Outdoor temperature K
\(U\) Wind speed at the weather station m/s
\(V\) Building volume m³
\(Q_s\) Stack-only infiltration m³/s
\(Q_w\) Wind-only infiltration m³/s
\(Q\) Combined infiltration m³/s
\(ACH\) Air changes per hour -
\(\dot Q_h\) Sensible heat loss W

Method and standards

Combined infiltration.

Where it is used

  • Heating load infiltration allowance.
  • Assessing airtightness improvements.

Common mistakes

  • Using leakage area at 10 Pa (EqLA) with 4 Pa coefficients.
  • Using wind at roof height instead of the weather station.

Assumptions and limits

  • Single zone; coefficients for the building's height and shelter.

References

  • Effective leakage area infiltration model

Questions and answers

Where does the leakage area come from?

A blower-door test, reporting effective leakage area at 4 Pa (ELA) or from n50 via a conversion.

Why add stack and wind in quadrature?

They act on the same openings with partly opposing pressure patterns; the root-sum-square fits measurements well.

What do the defaults represent?

An illustrative one-storey 400 m³ house with 500 cm² leakage area, 21 °C inside, −5 °C outside, 4.5 m/s wind.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Sherman and Grimsrud, Infiltration-Pressurization Correlation: Simplified Physical Modeling, ASHRAE Transactions 86 (1980)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.