Worked example
Example: Illustrative classroom. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Supply air CO₂ | 420.00 ppm |
| Exhaust (return) air CO₂ | 900.00 ppm |
| Breathing-zone CO₂ | 1,000.0 ppm |
| Number of occupants | 30.000 - |
| CO₂ generation per person | 0.005200 L/s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Contaminant removal effectiveness | 0.82759 |
| Outdoor air flow from the exhaust balance | 325.00 L/s |
| Outdoor air per person | 10.833 L/s |
| Flow that would give the breathing-zone level with perfect mixing | 268.97 L/s |
Open this example in the calculator and change any input.
Formula
\(Q_o = \frac{NG}{C_e - C_s}, \quad \varepsilon_c = \frac{C_e - C_s}{C_b - C_s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_s\) | Supply air CO₂ | - |
| \(C_e\) | Exhaust (return) air CO₂ | - |
| \(C_b\) | Breathing-zone CO₂ | - |
| \(N\) | Number of occupants | - |
| \(G\) | CO₂ generation per person | m³/s |
| \(\varepsilon_c\) | Contaminant removal effectiveness | - |
| \(Q_o\) | Outdoor air flow from the exhaust balance | m³/s |
| \(q_p\) | Outdoor air per person | m³/s |
| \(Q_{o,b}\) | Flow that would give the breathing-zone level with perfect mixing | m³/s |
Method and standards
CO₂ ventilation.
Where it is used
- Checking ventilation in occupied rooms with CO₂ monitors.
- Commissioning displacement and mixing systems.
Common mistakes
- Using readings before CO₂ has reached steady state.
- Ignoring outdoor CO₂ (about 420 ppm).
Assumptions and limits
- Steady state; constant occupancy; CO₂ only from occupants.
References
- Steady-state tracer balance and contaminant removal effectiveness
Questions and answers
Why use exhaust CO₂ for the flow?
All the CO₂ produced must leave in the exhaust, so the exhaust concentration gives the flow whatever the room distribution.
What effectiveness should be expected?
About 1.0 for well-mixed cooling, 0.8 for ceiling-supplied warm air, 1.2 or more for displacement ventilation.
What do the defaults represent?
An illustrative classroom of 30 people with 420 ppm supply, 900 ppm exhaust and 1,000 ppm in the breathing zone.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Etheridge and Sandberg, Building Ventilation: Theory and Measurement (Wiley, 1996)