Worked example
Example: Illustrative 500 L/s humid summer air. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Outdoor air flow | 500.00 L/s |
| Outdoor dry bulb | 35.000 °C |
| Room dry bulb | 24.000 °C |
| Outdoor humidity ratio | 18.000 g/kg |
| Room humidity ratio | 9.3000 g/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Sensible load | 6.8606 kW |
| Latent load | 13.055 kW |
| Total load | 19.916 kW |
| Total load in tons | 5.6630 TR |
Open this example in the calculator and change any input.
Formula
\(Q_s = \rho\dot V(1006 + 1860W_o)(T_o - T_i), \quad Q_l = \rho\dot V\,h_{fg}(W_o - W_i)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Outdoor air flow | m³/s |
| \(T_o\) | Outdoor dry bulb | K |
| \(T_i\) | Room dry bulb | K |
| \(W_o\) | Outdoor humidity ratio | kg/kg |
| \(W_i\) | Room humidity ratio | kg/kg |
| \(Q_s\) | Sensible load | W |
| \(Q_l\) | Latent load | W |
| \(Q_t\) | Total load | W |
| \(Q_{TR}\) | Total load in tons | W |
Method and standards
Outdoor air load.
Where it is used
- Ventilation design and AHU sizing.
- Energy recovery evaluation.
Common mistakes
- Forgetting the latent part.
- Using room RH instead of humidity ratio.
Assumptions and limits
- Standard air density; steady state.
References
- Sensible and latent air-load equations at standard density
Questions and answers
What load does 500 L/s of outdoor air at 35 °C add to a 24 °C room?
About 6.9 kW sensible and 13.1 kW latent at the default humidity: 19.9 kW, near 5.7 TR.
Why is the latent load so large?
Humid outdoor air carries much more water than room air, and removing it takes condensation heat.
What do the defaults represent?
An illustrative 500 L/s of outdoor air at 35 °C and 18 g/kg brought to a room at 24 °C and 9.3 g/kg.