Worked example
Example: Illustrative chilled ceiling 18 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Panel surface temperature | 18.000 °C |
| Mean temperature of other surfaces | 26.000 °C |
| Room air temperature | 25.000 °C |
| Panel emissivity | 90.000 % |
| Convective coefficient | 2.5000 W/(m²·K) |
| Active panel area | 60.000 m² |
Applying the formula below gives:
| Result | Value |
|---|---|
| Radiant flux (positive: into the panel = cooling) | 41.996 W/m² |
| Convective flux | 17.500 W/m² |
| Total flux | 59.496 W/m² |
| Panel capacity | 3.5698 kW |
| Radiant share | 70.586 % |
Open this example in the calculator and change any input.
Formula
\(q = \varepsilon\sigma\left(T_{AUST}^4 - T_p^4\right) + h_c(T_a - T_p)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_p\) | Panel surface temperature | K |
| \(T_{AUST}\) | Mean temperature of other surfaces | K |
| \(T_a\) | Room air temperature | K |
| \(\varepsilon\) | Panel emissivity | - |
| \(h_c\) | Convective coefficient | W/(m²·K) |
| \(A\) | Active panel area | m² |
| \(q_r\) | Radiant flux (positive: into the panel = cooling) | W/m² |
| \(q_c\) | Convective flux | W/m² |
| \(q\) | Total flux | W/m² |
| \(\dot Q\) | Panel capacity | W |
| \(q_r/q\) | Radiant share | - |
Method and standards
Radiant panels.
Where it is used
- Chilled ceiling and radiant floor design.
- Comfort heating of high spaces.
Common mistakes
- Ignoring dew point on cooled surfaces.
- Using a cooled-ceiling h_c for heated ceilings.
Assumptions and limits
- Panel sees the room as one grey surface at AUST.
References
- Radiant and convective panel exchange
Questions and answers
What limits a chilled ceiling?
Condensation: the surface must stay above the room dew point, which caps cooling at about 60–100 W/m².
Why are heated ceilings weak in convection?
Warm air stays at the ceiling, so convection from a heated ceiling is small; most output is radiant.
What do the defaults represent?
An illustrative 60 m² chilled ceiling at 18 °C in a 25 °C room with 26 °C surrounding surfaces.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.