Worked example
Example: Illustrative: 600 m3 room, 1.2 and 1.0 m2 openings, 3.5 m/s, Cp +0.6 / -0.3. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Windward opening area | 1.2000 m² |
| Leeward opening area | 1.0000 m² |
| Discharge coefficient (sharp opening 0.61) | 0.61000 - |
| Wind speed at building height | 3.5000 m/s |
| Pressure coefficient, windward face | 0.60000 - |
| Pressure coefficient, leeward face | -0.30000 - |
| Room or building volume | 600.00 m³ |
| Air density | 1.2000 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Effective opening area (openings in series) | 0.76822 m² |
| Wind pressure difference ½ρU²ΔC_p | 6.6150 Pa |
| Air flow | 5,601.5 m³/h |
| Air changes per hour | 9.3359 1/h |
| Mean velocity in the windward opening | 2.1257 m/s |
Open this example in the calculator and change any input.
Formula
\(Q = C_dA_{eff}U\sqrt{\Delta C_p}, \quad \frac{1}{A_{eff}^2} = \frac{1}{A_1^2} + \frac{1}{A_2^2}, \quad n = \frac{Q}{V}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A_1\) | Windward opening area | m² |
| \(A_2\) | Leeward opening area | m² |
| \(C_d\) | Discharge coefficient (sharp opening 0.61) | - |
| \(U\) | Wind speed at building height | m/s |
| \(C_{p1}\) | Pressure coefficient, windward face | - |
| \(C_{p2}\) | Pressure coefficient, leeward face | - |
| \(V\) | Room or building volume | m³ |
| \(\rho\) | Air density | kg/m³ |
| \(A_{eff}\) | Effective opening area (openings in series) | m² |
| \(\Delta p\) | Wind pressure difference ½ρU²ΔC_p | Pa |
| \(Q\) | Air flow | m³/s |
| \(n\) | Air changes per hour | 1/s |
| \(v_1\) | Mean velocity in the windward opening | m/s |
Method and standards
Wind-driven natural ventilation.
Where it is used
- Natural ventilation of offices, schools, warehouses and plant rooms.
- Comparing window and louvre sizes.
Common mistakes
- Adding opening areas instead of combining them in series.
- Using the meteorological wind speed without height and terrain correction.
Assumptions and limits
- Steady wind, sharp-edged openings, no stack effect.
References
- Wind-driven flow through openings in series (orifice equation)
Questions and answers
Why do the openings combine like resistances in series?
The same air passes through both; the pressure drop splits between them, so the effective area is 1/√(1/A₁² + 1/A₂²), dominated by the smaller opening.
What pressure coefficients are typical?
About +0.5 to +0.8 on a windward wall facing the wind and −0.2 to −0.5 on the leeward wall of a low building.
What do the defaults represent?
An illustrative 600 m³ room with 1.2 m² and 1.0 m² openings on opposite walls, 3.5 m/s wind and C_p of +0.6 and −0.3.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
ASHRAE Handbook – Fundamentals (ASHRAE, 2017), ch. 9 (thermal comfort) and ch. 16 (ventilation and infiltration), CIBSE AM10, Natural Ventilation in Non-Domestic Buildings (CIBSE, 2005)