Worked example
Example: Illustrative house slab. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Perimeter heat-loss factor (W per m per K) | 0.85000 W/(m·K) |
| Exposed slab perimeter | 44.000 m |
| Indoor design temperature | 21.000 °C |
| Outdoor design temperature | -10.000 °C |
| Heating degree-days (K·d) | 2,800.0 - |
| Heating system efficiency | 90.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Design heat loss | 1,159.4 W |
| Annual heat loss through the slab | 2,513.3 kWh |
| Annual heating input | 2,792.5 kWh |
Open this example in the calculator and change any input.
Formula
\(Q = F_pP(T_i - T_o), \quad E = F_pP\cdot HDD\cdot 24\ \text{h}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(F_p\) | Perimeter heat-loss factor (W per m per K) | W/(m·K) |
| \(P\) | Exposed slab perimeter | m |
| \(T_i\) | Indoor design temperature | K |
| \(T_o\) | Outdoor design temperature | K |
| \(HDD\) | Heating degree-days (K·d) | - |
| \(\eta\) | Heating system efficiency | - |
| \(Q\) | Design heat loss | W |
| \(E\) | Annual heat loss through the slab | J |
| \(E_f\) | Annual heating input | J |
Method and standards
Slab heat loss.
Where it is used
- Heating load of ground-floor rooms.
- Comparing edge insulation options.
Common mistakes
- Using floor area with a perimeter factor.
- Mixing W/m·K and Btu/h·ft·°F factors.
Assumptions and limits
- Perimeter factor from the design guide; steady state.
References
- Perimeter heat-loss method
Questions and answers
Why does the loss depend on perimeter, not area?
Deep ground under the middle of a slab is warm; most heat escapes through the short path at the edge.
Does edge insulation matter much?
Yes: it can halve or better the perimeter factor.
What do the defaults represent?
An illustrative house slab with 44 m exposed perimeter and F_p 0.85 W/m·K, 21 °C inside and −10 °C design, 2,800 degree-days.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
McQuiston, Parker, Spitler and Taherian, Heating, Ventilating and Air Conditioning, and ASHRAE, Principles of Heating, Ventilating and Air Conditioning, 8th ed. (ASHRAE, 2017)