Outdoor Air Rate for People and Floor Area

Breathing-zone outdoor air from a per-person and a per-area rate, corrected for air distribution effectiveness, with the outdoor-air fraction of the supply.

Food, dairy and textile

Inputs

Examples: Illustrative office 40 people 200 m2Classroom 30 pupils 70 m2Warehouse area only

Accepted: 0 to 100,000
Accepted: 0 to 50 L/s
Accepted: 1 to 1,000,000 m²
Accepted: 0 to 10 mm/s
Accepted: 30 to 120 %
Accepted: 10 to 1,000,000 L/s

Results

V_bz = R_p·P_z + R_a·A_z; V_oz = V_bz/E_z. Take R_p, R_a and E_z for the space type from the ventilation standard that applies; the defaults are typical office values.

Breathing-zone outdoor air160.00L/s
Zone outdoor air200.00L/s
Outdoor air per person5.0000L/s
Outdoor-air fraction of supply10.0000%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative office 40 people 200 m2. The inputs, in the units selected above:

InputValue
Occupants40.000 -
Outdoor air per person2.5000 L/s
Floor area200.00 m²
Outdoor air per m² of floor0.30000 mm/s
Air distribution effectiveness80.000 %
Supply air flow2,000.0 L/s

Applying the formula below gives:

ResultValue
Breathing-zone outdoor air160.00 L/s
Zone outdoor air200.00 L/s
Outdoor air per person5.0000 L/s
Outdoor-air fraction of supply10.0000 %

Open this example in the calculator and change any input.

Formula

\(\dot V_{bz} = R_pP_z + R_aA_z, \quad \dot V_{oz} = \frac{\dot V_{bz}}{E_z}\)

Variables

Symbol Meaning SI unit
\(P_z\) Occupants -
\(R_p\) Outdoor air per person m³/s
\(A_z\) Floor area m²
\(R_a\) Outdoor air per m² of floor m/s
\(E_z\) Air distribution effectiveness -
\(\dot V_s\) Supply air flow m³/s
\(\dot V_{bz}\) Breathing-zone outdoor air m³/s
\(\dot V_{oz}\) Zone outdoor air m³/s
\(\dot V_{oz}/P_z\) Outdoor air per person m³/s
\(\dot V_{oz}/\dot V_s\) Outdoor-air fraction of supply -

Method and standards

Ventilation rate.

Where it is used

  • Office, school and retail ventilation design.
  • Checking outdoor air in existing systems.

Common mistakes

  • Using only the per-person rate.
  • Forgetting distribution effectiveness.

Assumptions and limits

  • Steady occupancy; single zone.

References

  • Ventilation rate procedure (people plus area components)
  • ASHRAE Handbook of Fundamentals (ASHRAE)

Questions and answers

Why both per-person and per-area rates?

People emit CO₂ and odours; building materials and furnishings emit pollutants regardless of occupancy.

What is distribution effectiveness?

How well supply air reaches the breathing zone: ceiling supply of warm air mixes poorly (about 0.8); displacement ventilation can exceed 1.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.