Worked example
Example: Illustrative office 40 people 200 m2. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Occupants | 40.000 - |
| Outdoor air per person | 2.5000 L/s |
| Floor area | 200.00 m² |
| Outdoor air per m² of floor | 0.30000 mm/s |
| Air distribution effectiveness | 80.000 % |
| Supply air flow | 2,000.0 L/s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Breathing-zone outdoor air | 160.00 L/s |
| Zone outdoor air | 200.00 L/s |
| Outdoor air per person | 5.0000 L/s |
| Outdoor-air fraction of supply | 10.0000 % |
Open this example in the calculator and change any input.
Formula
\(\dot V_{bz} = R_pP_z + R_aA_z, \quad \dot V_{oz} = \frac{\dot V_{bz}}{E_z}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_z\) | Occupants | - |
| \(R_p\) | Outdoor air per person | m³/s |
| \(A_z\) | Floor area | m² |
| \(R_a\) | Outdoor air per m² of floor | m/s |
| \(E_z\) | Air distribution effectiveness | - |
| \(\dot V_s\) | Supply air flow | m³/s |
| \(\dot V_{bz}\) | Breathing-zone outdoor air | m³/s |
| \(\dot V_{oz}\) | Zone outdoor air | m³/s |
| \(\dot V_{oz}/P_z\) | Outdoor air per person | m³/s |
| \(\dot V_{oz}/\dot V_s\) | Outdoor-air fraction of supply | - |
Method and standards
Ventilation rate.
Where it is used
- Office, school and retail ventilation design.
- Checking outdoor air in existing systems.
Common mistakes
- Using only the per-person rate.
- Forgetting distribution effectiveness.
Assumptions and limits
- Steady occupancy; single zone.
References
- Ventilation rate procedure (people plus area components)
- ASHRAE Handbook of Fundamentals (ASHRAE)
Questions and answers
Why both per-person and per-area rates?
People emit CO₂ and odours; building materials and furnishings emit pollutants regardless of occupancy.
What is distribution effectiveness?
How well supply air reaches the breathing zone: ceiling supply of warm air mixes poorly (about 0.8); displacement ventilation can exceed 1.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.