Worked example
Example: Illustrative hot workshop: 26 / 40 / 33 C indoors. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Exposure | Indoors or outdoors without sun |
| Natural wet-bulb temperature | 26.000 °C |
| Black globe temperature | 40.000 °C |
| Air (dry-bulb) temperature | 33.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Wet bulb globe temperature | 30.200 °C |
| Indoor formula 0.7t_nw + 0.3t_g | 30.200 °C |
| Outdoor formula 0.7t_nw + 0.2t_g + 0.1t_a | 29.500 °C |
Open this example in the calculator and change any input.
Formula
\(WBGT_{in} = 0.7t_{nw} + 0.3t_g, \quad WBGT_{out} = 0.7t_{nw} + 0.2t_g + 0.1t_a\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{location}\) | Exposure | - |
| \(t_{nw}\) | Natural wet-bulb temperature | K |
| \(t_g\) | Black globe temperature | K |
| \(t_a\) | Air (dry-bulb) temperature | K |
| \(WBGT\) | Wet bulb globe temperature | K |
| \(WBGT_{in}\) | Indoor formula 0.7t_nw + 0.3t_g | K |
| \(WBGT_{out}\) | Outdoor formula 0.7t_nw + 0.2t_g + 0.1t_a | K |
Method and standards
WBGT heat-stress index.
Where it is used
- Foundries, boiler houses, kitchens and outdoor work.
- Sports and military training heat management.
Common mistakes
- Using the psychrometric (aspirated) wet bulb instead of the natural wet bulb.
- Using the indoor formula in direct sun.
Assumptions and limits
- Instruments to the usual specification (150 mm black globe, natural wet bulb).
References
- Wet bulb globe temperature index
Questions and answers
Why does the wet bulb carry 70 % of the weight?
Sweat evaporation is the body's main cooling route in heat; the natural wet bulb reflects humidity, wind and radiation on a wetted surface.
Is WBGT the same as the heat index?
No: the heat index uses air temperature and humidity in shade; WBGT also counts radiant heat and wind, so it suits work in sun and near hot plant.
What do the defaults represent?
An illustrative hot workshop: natural wet bulb 26 °C, globe 40 °C and air 33 °C, indoors.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Yaglou and Minard, Control of heat casualties at military training centers, AMA Arch. Ind. Health 16 (1957) 302–316, Parsons, Human Thermal Environments, 3rd ed. (CRC Press, 2014), ch. 9