Worked example
Example: Illustrative balanced 4 m3/s loop. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Exhaust air flow | 14,400 m³/h |
| Supply (outdoor) air flow | 14,400 m³/h |
| Exhaust air temperature | 22.000 °C |
| Outdoor air temperature | -10.000 °C |
| Exhaust coil UA | 9.0000 kW/K |
| Supply coil UA | 9.0000 kW/K |
| Liquid capacity rate ṁc_p | 4.8000 kW/K |
Applying the formula below gives:
| Result | Value |
|---|---|
| Exhaust coil effectiveness | 65.344 % |
| Supply coil effectiveness | 65.344 % |
| Heat recovered | 74.537 kW |
| Overall effectiveness | 48.237 % |
| Supply air leaving the coil | 5.4360 °C |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \frac{T_e - T_s}{\frac{1}{\varepsilon_eC_{min,e}} + \frac{1}{\varepsilon_sC_{min,s}} - \frac{1}{C_l}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_e\) | Exhaust air flow | m³/s |
| \(\dot V_s\) | Supply (outdoor) air flow | m³/s |
| \(T_e\) | Exhaust air temperature | K |
| \(T_s\) | Outdoor air temperature | K |
| \(UA_e\) | Exhaust coil UA | W/K |
| \(UA_s\) | Supply coil UA | W/K |
| \(C_l\) | Liquid capacity rate ṁc_p | W/K |
| \(\varepsilon_e\) | Exhaust coil effectiveness | - |
| \(\varepsilon_s\) | Supply coil effectiveness | - |
| \(\dot Q\) | Heat recovered | W |
| \(\varepsilon_o\) | Overall effectiveness | - |
| \(T_{s,out}\) | Supply air leaving the coil | K |
Method and standards
Run-around loop.
Where it is used
- Heat recovery in hospitals, labs and separated air handlers.
- Choosing glycol pump flow.
Common mistakes
- Using equal effectiveness for coils of different size.
- Ignoring frost control on the exhaust coil.
Assumptions and limits
- Counterflow coils; sensible heat only; constant properties.
References
- Coupled exchangers by ε–NTU
Questions and answers
Why use a run-around loop rather than a wheel?
The supply and exhaust ducts can be far apart and there is no cross-contamination.
What glycol flow is best?
One giving a liquid capacity rate near the air capacity rate; too little or too much both lower recovery.
What do the defaults represent?
An illustrative 4 m³/s supply and exhaust, 22 °C exhaust, −10 °C outdoor, coils of 9 kW/K and a glycol loop of 4.8 kW/K.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Kays and London, Compact Heat Exchangers, 3rd ed. (McGraw-Hill, 1984)