Night Purge Ventilation Cooling Energy

Cooling delivered by night-time ventilation of a building from the air flow, indoor and outdoor temperatures and hours, against the fan energy used.

Food, dairy and textile

Inputs

Examples: Illustrative 3 m3/s, 25 to 17 C for 8 hNatural ventilation, no fansSmall 4 K difference

Accepted: 36 to 3,600,000 m³/h
Accepted: 10 to 40 °C
Accepted: -10 to 40 °C
Accepted: 10 to 100 %
Accepted: 0 to 24 h
Accepted: 0 to 10 kJ/m³
Accepted: 60 to 110 kPa

Results

Q = ε·ρ·V̇·c_p·(T_i − T_o); ε covers how closely exhaust air approaches the mean indoor temperature. Exposed thermal mass (concrete soffits) is needed to store the coolth for the next day.

Mean cooling power6.7837kW
Cooling per night40.702kWh
Fan energy per night18.000kWh
Cooling per unit of fan energy2.2612

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 3 m3/s, 25 to 17 C for 8 h. The inputs, in the units selected above:

InputValue
Purge air flow10,800 m³/h
Mean indoor (exhaust) temperature25.000 °C
Mean outdoor temperature at night17.000 °C
Heat removal effectiveness70.000 %
Purge hours per night8.0000 h
Specific fan power1.0000 kJ/m³
Atmospheric pressure101.33 kPa

Applying the formula below gives:

ResultValue
Mean cooling power20.562 kW
Cooling per night164.49 kWh
Fan energy per night24.000 kWh
Cooling per unit of fan energy6.8539

Open this example in the calculator and change any input.

Formula

\(\dot Q_c = \varepsilon\rho\dot Vc_p(T_i - T_o), \quad E_f = SFP\cdot\dot V\cdot t\)

Variables

Symbol Meaning SI unit
\(\dot V\) Purge air flow m³/s
\(T_i\) Mean indoor (exhaust) temperature K
\(T_o\) Mean outdoor temperature at night K
\(\varepsilon\) Heat removal effectiveness -
\(t\) Purge hours per night s
\(SFP\) Specific fan power J/m³
\(p\) Atmospheric pressure Pa
\(\dot Q_c\) Mean cooling power W
\(E_c\) Cooling per night J
\(E_f\) Fan energy per night J
\(E_c/E_f\) Cooling per unit of fan energy -

Method and standards

Night purge.

Where it is used

  • Low-energy office cooling strategies.
  • Overheating mitigation.

Common mistakes

  • Ignoring fan energy.
  • Purging with humid outdoor air.

Assumptions and limits

  • Mean temperatures over the purge period.

References

  • Sensible heat removal by ventilation
  • CIBSE Guide A
  • Environmental Design (CIBSE)

Questions and answers

Is night purge worth the fan energy?

Usually, when nights are at least 5 K cooler than the building: each kWh of fan energy typically removes 5–15 kWh of heat.

What limits it?

Small temperature differences, humid nights, security of open windows and lack of exposed thermal mass.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.