Worked example
Example: Illustrative 3 m3/s, 25 to 17 C for 8 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Purge air flow | 10,800 m³/h |
| Mean indoor (exhaust) temperature | 25.000 °C |
| Mean outdoor temperature at night | 17.000 °C |
| Heat removal effectiveness | 70.000 % |
| Purge hours per night | 8.0000 h |
| Specific fan power | 1.0000 kJ/m³ |
| Atmospheric pressure | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Mean cooling power | 20.562 kW |
| Cooling per night | 164.49 kWh |
| Fan energy per night | 24.000 kWh |
| Cooling per unit of fan energy | 6.8539 |
Open this example in the calculator and change any input.
Formula
\(\dot Q_c = \varepsilon\rho\dot Vc_p(T_i - T_o), \quad E_f = SFP\cdot\dot V\cdot t\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Purge air flow | m³/s |
| \(T_i\) | Mean indoor (exhaust) temperature | K |
| \(T_o\) | Mean outdoor temperature at night | K |
| \(\varepsilon\) | Heat removal effectiveness | - |
| \(t\) | Purge hours per night | s |
| \(SFP\) | Specific fan power | J/m³ |
| \(p\) | Atmospheric pressure | Pa |
| \(\dot Q_c\) | Mean cooling power | W |
| \(E_c\) | Cooling per night | J |
| \(E_f\) | Fan energy per night | J |
| \(E_c/E_f\) | Cooling per unit of fan energy | - |
Method and standards
Night purge.
Where it is used
- Low-energy office cooling strategies.
- Overheating mitigation.
Common mistakes
- Ignoring fan energy.
- Purging with humid outdoor air.
Assumptions and limits
- Mean temperatures over the purge period.
References
- Sensible heat removal by ventilation
- CIBSE Guide A
- Environmental Design (CIBSE)
Questions and answers
Is night purge worth the fan energy?
Usually, when nights are at least 5 K cooler than the building: each kWh of fan energy typically removes 5–15 kWh of heat.
What limits it?
Small temperature differences, humid nights, security of open windows and lack of exposed thermal mass.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.