Earth–Air Heat Exchanger (Earth Tube) Outlet Temperature

Outlet air temperature, effectiveness and heat exchanged by a buried pipe of given length and diameter, from the air speed and the undisturbed soil temperature.

Inputs

Examples: Illustrative 40 m pipe, summer pre-coolingWinter pre-heating, 60 mSmall pipe, low velocity

Accepted: 20 to 2,000 mm
Accepted: 1 to 1,000 m
Accepted: 0.1 to 20 m/s
Accepted: -43.15 to 56.85 °C
Accepted: -23.15 to 46.85 °C

Results

Air flowing through a pipe whose wall stays at the soil temperature approaches it exponentially: T_out = T_soil + (T_in − T_soil)e^(−NTU) with NTU = hπDL/(ṁc_p). The convective coefficient uses the Dittus–Boelter correlation (Nu = 0.023Re^0.8Pr^0.4) for turbulent flow and Nu = 3.66 for laminar flow, with air properties near 20 °C. In long operation the soil around the pipe warms (or cools), so real effectiveness falls over a season; space pipes about 3–5 diameters apart and bury them 2–3 m deep.

Reynolds number39,578
Convective coefficient12.298W/(m²·K)
Effectiveness 1 − e^(−NTU)93.330%
Outlet air temperature26.934°C
Heat exchanged with the soil1.4916kW
Air flow339.29m³/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 40 m pipe, summer pre-cooling. The inputs, in the units selected above:

InputValue
Pipe inner diameter200.00 mm
Pipe length40.000 m
Air velocity in the pipe3.0000 m/s
Inlet (outdoor) air temperature40.000 °C
Pipe wall (soil) temperature26.000 °C

Applying the formula below gives:

ResultValue
Reynolds number39,578
Convective coefficient12.298 W/(m²·K)
Effectiveness 1 − e^(−NTU)93.330 %
Outlet air temperature26.934 °C
Heat exchanged with the soil1.4916 kW
Air flow339.29 m³/h

Open this example in the calculator and change any input.

Formula

\(T_{out} = T_{soil} + (T_{in} - T_{soil})e^{-NTU}, \quad NTU = \frac{h\pi DL}{\dot mc_p}, \quad Nu = 0.023Re^{0.8}Pr^{0.4}\)

Variables

Symbol Meaning SI unit
\(D\) Pipe inner diameter m
\(L\) Pipe length m
\(u\) Air velocity in the pipe m/s
\(T_{in}\) Inlet (outdoor) air temperature K
\(T_{soil}\) Pipe wall (soil) temperature K
\(Re\) Reynolds number -
\(h\) Convective coefficient W/(m²·K)
\(\varepsilon\) Effectiveness 1 − e^(−NTU) -
\(T_{out}\) Outlet air temperature K
\(\dot Q\) Heat exchanged with the soil W
\(\dot V\) Air flow m³/s

Method and standards

Earth tube.

Where it is used

  • Passive pre-cooling and pre-heating of ventilation air.
  • Sizing earth–air tunnels for buildings and farms.

Common mistakes

  • Assuming the soil stays at its undisturbed temperature indefinitely.
  • Ignoring condensation in humid climates.

Assumptions and limits

  • Constant wall temperature; smooth pipe; dry air properties.

References

  • Constant wall temperature pipe flow (ε–NTU) with Dittus–Boelter

Questions and answers

What soil temperature should I use?

The undisturbed ground temperature at the pipe depth for the season, close to the annual mean air temperature at 3–4 m.

Why does performance fall over a summer?

The soil around the pipe heats up, so the wall is warmer than the undisturbed soil.

What do the defaults represent?

An illustrative 40 m, 200 mm pipe with air at 3 m/s entering at 40 °C, soil at 26 °C.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Incropera, DeWitt, Bergman and Lavine, Fundamentals of Heat and Mass Transfer, 7th ed. (Wiley, 2011)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.