Worked example
Example: Illustrative 12 kW house, COP 4, 50 W/m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heat pump heating capacity | 12.000 kW |
| Coefficient of performance | 4.0000 - |
| Specific heat extraction rate of the ground (W per m of borehole) | 50.000 W/m |
| Maximum depth per borehole | 100.00 m |
| Full-load hours per year | 1,800.0 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat extracted from the ground | 9.0000 kW |
| Total borehole length | 180.00 m |
| Number of boreholes | 2.0000 |
| Heat extracted per year | 16.200 MWh |
| Annual extraction per metre (kWh/m) | 90.000 |
| Compressor electrical power | 3.0000 kW |
Open this example in the calculator and change any input.
Formula
\(\dot Q_g = \dot Q_h\left(1 - \frac{1}{COP}\right), \quad L = \frac{\dot Q_g}{q'}, \quad n = \left\lceil\frac{L}{H}\right\rceil\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q_h\) | Heat pump heating capacity | W |
| \(COP\) | Coefficient of performance | - |
| \(q'\) | Specific heat extraction rate of the ground (W per m of borehole) | W/m |
| \(H\) | Maximum depth per borehole | m |
| \(t_{fl}\) | Full-load hours per year | s |
| \(\dot Q_g\) | Heat extracted from the ground | W |
| \(L\) | Total borehole length | m |
| \(n\) | Number of boreholes | - |
| \(E_g\) | Heat extracted per year | J |
| \(E_g/L\) | Annual extraction per metre (kWh/m) | - |
| \(P_{el}\) | Compressor electrical power | W |
Method and standards
Borehole field sizing.
Where it is used
- Small ground-source heat pump design.
- Feasibility of geothermal heating.
Common mistakes
- Sizing on the heating output instead of the ground load.
- Using high W/m values for dry ground.
Assumptions and limits
- Heating-dominated load; rule-of-thumb extraction rate.
References
- Specific heat-extraction sizing of borehole heat exchangers
Questions and answers
Why does the ground supply less than the heating output?
The heat pump's electricity also becomes heat, so the ground supplies only Q(1 − 1/COP), three-quarters at a COP of 4.
How deep are boreholes?
Usually 80–200 m, spaced at least 6–10 m apart so they do not cool each other.
What do the defaults represent?
An illustrative 12 kW house heat pump at COP 4 in rock giving 50 W/m, boreholes up to 100 m, 1,800 full-load hours.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Kothari, Singal and Ranjan, Renewable Energy Sources and Emerging Technologies, 2nd ed. (PHI, 2011)