Chlorine Dose for Coliform Kill by the Collins-Selleck Model

Combined chlorine residual for a coliform target by the refined Collins-Selleck model, and the dose including immediate demand and decay in the contact tank.

Refinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Reuse 2.2 per 100 mL, 90 min

Accepted: 1 to 1E+10
Accepted: 0.001 to 100,000,000
Accepted: 1 to 600 min
Accepted: 0.5 to 6
Accepted: 0.01 to 100
Accepted: 0 to 50 mg/L
Accepted: 0 to 50 mg/L

Results

N/N₀ = (CT/b)^(−n) for CT above b (no kill below the shoulder). The typical values for combined chlorine on secondary effluent are n = 2.8 and b = 4.0 mg·min/L; confirm them by testing the actual effluent.

Required CT419.40
Required combined residual4.6599mg/L
Chlorine dose7.1599mg/L

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Reuse 2.2 per 100 mL, 90 min. The inputs, in the units selected above:

InputValue
Coliform before disinfection (per 100 mL)1,000,000 -
Coliform target (per 100 mL)2.2000 -
Contact time90.000 min
Slope n2.8000 -
Lag (shoulder) CT, mg·min/L4.0000 -
Immediate chlorine demand1.5000 mg/L
Decay in the contact tank1.0000 mg/L

Applying the formula below gives:

ResultValue
Required CT419.40
Required combined residual4.6599 mg/L
Chlorine dose7.1599 mg/L

Open this example in the calculator and change any input.

Formula

\(\frac{N}{N_o} = \left(\frac{CT}{b}\right)^{-n}, \quad C = \frac{b}{t}\left(\frac{N}{N_o}\right)^{-1/n}, \quad C_{dose} = C + D_i + D_d\)

Variables

Symbol Meaning SI unit
\(N_o\) Coliform before disinfection (per 100 mL) -
\(N\) Coliform target (per 100 mL) -
\(t\) Contact time s
\(n\) Slope n -
\(b\) Lag (shoulder) CT, mg·min/L -
\(D_i\) Immediate chlorine demand kg/m³
\(D_d\) Decay in the contact tank kg/m³
\(CT\) Required CT -
\(C\) Required combined residual kg/m³
\(C_{dose}\) Chlorine dose kg/m³

Method and standards

Refined Collins-Selleck model.

Where it is used

  • Chlorination design for reuse and discharge permits.
  • Seasonal dose planning.

Common mistakes

  • Using free chlorine coefficients for combined chlorine.
  • Leaving out decay in the contact tank.

Assumptions and limits

  • Coefficients site-specific; combined chlorine.

Questions and answers

Why is the model different from Chick's law?

Combined chlorine shows a lag (shoulder) before kill starts and a tailing kill rate; the Collins-Selleck power law fits this better for wastewater.

What makes up the dose?

The residual needed for the kill, plus the immediate demand of the effluent, plus what decays in the contact tank over the contact time.

What do the defaults represent?

An illustrative case: Reuse 2.2 per 100 mL, 90 min. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Metcalf and Eddy (Tchobanoglous, Stensel, Tsuchihashi and Burton), Wastewater Engineering: Treatment and Resource Recovery, 5th ed. (McGraw-Hill, 2014), sec. 12-3, eq. 12-27 and Example 12-4

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.