FireCADCalc

Window U-Value from Glass, Frame and Edge (Area-Weighted)

Overall window U-value from the glazing and frame U-values and the glass edge linear thermal transmittance, weighted by areas and edge length.

Inputs

Examples: Illustrative reference windowSmall triple-glazed window, warm edgeAluminium patio door

Accepted: 0.1 to 20 m
Accepted: 0.1 to 20 m
Accepted: 10 to 500 mm
Accepted: 0.1 to 10 W/(m²·K)
Accepted: 0.1 to 10 W/(m²·K)
Accepted: 0 to 1 W/(m·K)
Accepted: 0 to 100 K

Results

The window's U-value is the area-weighted average of glass and frame plus the extra heat flow at the glass edge, where the spacer bridges the panes: U_w = (A_gU_g + A_fU_f + l_gΨ_g)/(A_g + A_f) (the method of ISO 10077-1). Small windows have a larger frame share and edge length per area, so their U_w is worse than the glass figure suggests; warm-edge spacers reduce Ψ_g from about 0.08 to 0.04 W/m·K.

Glazed area4.5696m²
Frame area0.71040m²
Glass edge perimeter8.5600m
Window U-value1.8122W/(m²·K)
Heat loss through the window191.37W

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative reference window. The inputs, in the units selected above:

InputValue
Window width (overall)1.2300 m
Window height (overall)1.4800 m
Frame face width (uniform)110.00 mm
Glazing centre U-value1.1000 W/(m²·K)
Frame U-value1.4000 W/(m²·K)
Edge linear thermal transmittance0.060000 W/(m·K)
Inside–outside temperature difference20.000 K

Applying the formula below gives:

ResultValue
Glazed area1.2726 m²
Frame area0.54780 m²
Glass edge perimeter4.5400 m
Window U-value1.3399 W/(m²·K)
Heat loss through the window48.784 W

Open this example in the calculator and change any input.

Formula

\(U_w = \frac{A_gU_g + A_fU_f + l_g\Psi_g}{A_g + A_f}\)

Variables

Symbol Meaning SI unit
\(W\) Window width (overall) m
\(H\) Window height (overall) m
\(b_f\) Frame face width (uniform) m
\(U_g\) Glazing centre U-value W/(m²·K)
\(U_f\) Frame U-value W/(m²·K)
\(\Psi_g\) Edge linear thermal transmittance W/(m·K)
\(\Delta T\) Inside–outside temperature difference K
\(A_g\) Glazed area m²
\(A_f\) Frame area m²
\(l_g\) Glass edge perimeter m
\(U_w\) Window U-value W/(m²·K)
\(\dot Q\) Heat loss through the window W

Method and standards

Window U-value.

Where it is used

  • Envelope compliance and heat loss.
  • Comparing frame and spacer options.

Common mistakes

  • Using the glazing U-value for the whole window.
  • Forgetting the edge term.

Assumptions and limits

  • Uniform frame width; one glazed pane unit.

References

  • Area-weighted window thermal transmittance
  • ISO 10077-1
  • Thermal performance of windows
  • doors and shutters: Calculation of thermal transmittance
  • Part 1 (method equation)

Questions and answers

Why is the window U-value worse than the glass U-value?

Frames usually conduct more than modern glazing, and the spacer adds an edge heat flow.

What is Ψ_g?

The extra heat flow per metre of glass edge caused by the spacer and frame interaction.

What do the defaults represent?

An illustrative 1.23 × 1.48 m window, 110 mm frame, U_g = 1.1, U_f = 1.4 W/m²·K, Ψ = 0.06 W/m·K at 20 K.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.