Worked example
Example: Illustrative 0.6 m overhang, sun at 60 degrees. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Overhang projection | 0.60000 m |
| Gap from overhang to window head | 0.30000 m |
| Window height | 1.5000 m |
| Window width | 1.8000 m |
| Solar altitude | 60.000 ° |
| Wall-solar azimuth (sun relative to wall normal) | 20.000 ° |
Applying the formula below gives:
| Result | Value |
|---|---|
| Profile (vertical shadow) angle | 61.519 ° |
| Shadow depth below the overhang | 1.1059 m |
| Shaded fraction of the window | 53.728 % |
| Sunlit glass area | 1.2493 m² |
Open this example in the calculator and change any input.
Formula
\(\tan\Omega = \frac{\tan\beta}{\cos\gamma}, \quad y = P\tan\Omega, \quad f_s = \frac{\min(H, \max(0, y - G))}{H}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | Overhang projection | m |
| \(G\) | Gap from overhang to window head | m |
| \(H\) | Window height | m |
| \(W\) | Window width | m |
| \(\beta\) | Solar altitude | rad |
| \(\gamma\) | Wall-solar azimuth (sun relative to wall normal) | rad |
| \(\Omega\) | Profile (vertical shadow) angle | rad |
| \(y\) | Shadow depth below the overhang | m |
| \(f_s\) | Shaded fraction of the window | - |
| \(A_{sun}\) | Sunlit glass area | m² |
Method and standards
Overhang shading.
Where it is used
- Passive solar design and cooling load reduction.
- Checking shading at design hours.
Common mistakes
- Using the solar altitude instead of the profile angle off-normal.
- Ignoring the gap above the window.
Assumptions and limits
- Infinitely long overhang; direct beam only.
References
- Shading by horizontal projections
Questions and answers
What overhang depth shades a window fully at noon in summer?
Projection = (gap + window height)/tan Ω at the design sun position.
Why does an overhang not work on a west wall?
The afternoon sun is low, so the profile angle is small and the shadow barely reaches the glass.
What do the defaults represent?
An illustrative 0.6 m overhang, 0.3 m above a 1.5 × 1.8 m window, sun at 60° altitude and 20° off the wall normal.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
McQuiston, Parker, Spitler and Taherian, Heating, Ventilating and Air Conditioning, and ASHRAE, Principles of Heating, Ventilating and Air Conditioning, 8th ed. (ASHRAE, 2017)