Thermal Comfort: Predicted Mean Vote (PMV) and PPD

Fanger's predicted mean vote and predicted percentage dissatisfied from air and radiant temperature, air speed, humidity, metabolic rate and clothing insulation.

Inputs

Examples: Illustrative office: 24 C air, 25 C radiant, 0.15 m/s, 50 %, 1.1 met, 0.6 cloWinter office 21 C, 1.0 clo, 1.2 metWarm workshop 28 C, 30 C radiant, 0.4 m/s, 2.0 met, 0.6 clo

Accepted: -10 to 50 °C
Accepted: -10 to 70 °C
Accepted: 0 to 2 m/s
Accepted: 0 to 100 %
Accepted: 0.8 to 4
Accepted: 0 to 2

Results

Fanger's heat-balance model (no external work). Valid for PMV between −2 and +2, 10–30 °C air, 0.8–4 met and 0–2 clo. Comfort categories commonly use |PMV| < 0.5 (PPD < 10 %).

Predicted mean vote (−3 cold to +3 hot)-0.27591
Predicted percentage dissatisfied6.5810%
Clothing surface temperature25.976°C
Convective heat transfer coefficient3.8264W/(m²·K)
Operative temperature (mean of air and radiant)20.500°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative office: 24 C air, 25 C radiant, 0.15 m/s, 50 %, 1.1 met, 0.6 clo. The inputs, in the units selected above:

InputValue
Air temperature24.000 °C
Mean radiant temperature25.000 °C
Relative air speed0.15000 m/s
Relative humidity50.000 %
Metabolic rate (1 met = 58.15 W/m²; office 1.1–1.2)1.1000 -
Clothing insulation (summer 0.5, winter 1.0 clo)0.60000 -

Applying the formula below gives:

ResultValue
Predicted mean vote (−3 cold to +3 hot)-0.26020
Predicted percentage dissatisfied6.4057 %
Clothing surface temperature29.374 °C
Convective heat transfer coefficient4.6863 W/(m²·K)
Operative temperature (mean of air and radiant)24.500 °C

Open this example in the calculator and change any input.

Formula

\(PMV = (0.303e^{-0.036M} + 0.028)\left[(M - W) - H_{evap} - H_{resp} - 3.96\times10^{-8}f_{cl}\left[(t_{cl} + 273)^4 - (\bar t_r + 273)^4\right] - f_{cl}h_c(t_{cl} - t_a)\right]\)

\(PPD = 100 - 95\exp\left(-0.03353PMV^4 - 0.2179PMV^2\right)\)

Variables

Symbol Meaning SI unit
\(t_a\) Air temperature K
\(\bar t_r\) Mean radiant temperature K
\(v_{ar}\) Relative air speed m/s
\(RH\) Relative humidity -
\(M\) Metabolic rate (1 met = 58.15 W/m²; office 1.1–1.2) -
\(I_{cl}\) Clothing insulation (summer 0.5, winter 1.0 clo) -
\(PMV\) Predicted mean vote (−3 cold to +3 hot) -
\(PPD\) Predicted percentage dissatisfied -
\(t_{cl}\) Clothing surface temperature K
\(h_c\) Convective heat transfer coefficient W/(m²·K)
\(t_o\) Operative temperature (mean of air and radiant) K

Method and standards

Fanger's heat-balance comfort model.

Where it is used

  • Office, school and hospital HVAC design and audits.
  • Comfort complaints and set-point decisions.

Common mistakes

  • Using air temperature as the radiant temperature near cold windows.
  • Forgetting the clothing and activity of the occupants.

Assumptions and limits

  • Steady state, moderate environments, no external work.

References

  • Fanger's predicted mean vote and predicted percentage dissatisfied (the ISO 7730 and ASHRAE 55 method)

Questions and answers

Why is PPD never below 5 %?

Even at a neutral vote some people feel too warm or too cool; Fanger's surveys found a minimum of about 5 % dissatisfied.

What changes comfort most?

Clothing and activity: 0.5 clo more or 0.2 met more each shift the neutral temperature by roughly 2–3 °C.

What do the defaults represent?

An illustrative office: 24 °C air, 25 °C radiant, 0.15 m/s, 50 % humidity, 1.1 met and 0.6 clo.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Fanger, Thermal Comfort: Analysis and Applications in Environmental Engineering (Danish Technical Press, 1970), ASHRAE Handbook – Fundamentals (ASHRAE, 2017), ch. 9 (thermal comfort) and ch. 16 (ventilation and infiltration)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.