Worked example
Example: Illustrative office: 24 C air, 25 C radiant, 0.15 m/s, 50 %, 1.1 met, 0.6 clo. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air temperature | 24.000 °C |
| Mean radiant temperature | 25.000 °C |
| Relative air speed | 0.15000 m/s |
| Relative humidity | 50.000 % |
| Metabolic rate (1 met = 58.15 W/m²; office 1.1–1.2) | 1.1000 - |
| Clothing insulation (summer 0.5, winter 1.0 clo) | 0.60000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Predicted mean vote (−3 cold to +3 hot) | -0.26020 |
| Predicted percentage dissatisfied | 6.4057 % |
| Clothing surface temperature | 29.374 °C |
| Convective heat transfer coefficient | 4.6863 W/(m²·K) |
| Operative temperature (mean of air and radiant) | 24.500 °C |
Open this example in the calculator and change any input.
Formula
\(PMV = (0.303e^{-0.036M} + 0.028)\left[(M - W) - H_{evap} - H_{resp} - 3.96\times10^{-8}f_{cl}\left[(t_{cl} + 273)^4 - (\bar t_r + 273)^4\right] - f_{cl}h_c(t_{cl} - t_a)\right]\)
\(PPD = 100 - 95\exp\left(-0.03353PMV^4 - 0.2179PMV^2\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(t_a\) | Air temperature | K |
| \(\bar t_r\) | Mean radiant temperature | K |
| \(v_{ar}\) | Relative air speed | m/s |
| \(RH\) | Relative humidity | - |
| \(M\) | Metabolic rate (1 met = 58.15 W/m²; office 1.1–1.2) | - |
| \(I_{cl}\) | Clothing insulation (summer 0.5, winter 1.0 clo) | - |
| \(PMV\) | Predicted mean vote (−3 cold to +3 hot) | - |
| \(PPD\) | Predicted percentage dissatisfied | - |
| \(t_{cl}\) | Clothing surface temperature | K |
| \(h_c\) | Convective heat transfer coefficient | W/(m²·K) |
| \(t_o\) | Operative temperature (mean of air and radiant) | K |
Method and standards
Fanger's heat-balance comfort model.
Where it is used
- Office, school and hospital HVAC design and audits.
- Comfort complaints and set-point decisions.
Common mistakes
- Using air temperature as the radiant temperature near cold windows.
- Forgetting the clothing and activity of the occupants.
Assumptions and limits
- Steady state, moderate environments, no external work.
References
- Fanger's predicted mean vote and predicted percentage dissatisfied (the ISO 7730 and ASHRAE 55 method)
Questions and answers
Why is PPD never below 5 %?
Even at a neutral vote some people feel too warm or too cool; Fanger's surveys found a minimum of about 5 % dissatisfied.
What changes comfort most?
Clothing and activity: 0.5 clo more or 0.2 met more each shift the neutral temperature by roughly 2–3 °C.
What do the defaults represent?
An illustrative office: 24 °C air, 25 °C radiant, 0.15 m/s, 50 % humidity, 1.1 met and 0.6 clo.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Fanger, Thermal Comfort: Analysis and Applications in Environmental Engineering (Danish Technical Press, 1970), ASHRAE Handbook – Fundamentals (ASHRAE, 2017), ch. 9 (thermal comfort) and ch. 16 (ventilation and infiltration)