Outdoor (Fresh) Air Load: Sensible, Latent and Total

Sensible, latent and total cooling load of bringing outdoor ventilation air to room conditions, from air flow, temperatures and humidity ratios.

Inputs

Examples: Illustrative 500 L/s humid summer airHot dry climateOffice, 200 L/s

Accepted: 1 to 100,000 L/s
Accepted: -10 to 50 °C
Accepted: 10 to 30 °C
Accepted: 0 to 40 g/kg
Accepted: 0 to 30 g/kg

Results

Ventilation air must be cooled from outdoor to room temperature (sensible load) and dried from outdoor to room humidity ratio (latent load, at about 2,501 kJ per kg of water). Taking standard air density 1.2 kg/m³, a litre per second at 1 K is about 1.2 W sensible. In humid climates the latent part can exceed the sensible, which is why dedicated outdoor-air units and energy recovery pay off. Negative values mean the air helps cool or dry.

Sensible load2.2533kW
Latent load6.6026kW
Total load8.8560kW
Total load in tons2.5181TR

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 500 L/s humid summer air. The inputs, in the units selected above:

InputValue
Outdoor air flow500.00 L/s
Outdoor dry bulb35.000 °C
Room dry bulb24.000 °C
Outdoor humidity ratio18.000 g/kg
Room humidity ratio9.3000 g/kg

Applying the formula below gives:

ResultValue
Sensible load6.8606 kW
Latent load13.055 kW
Total load19.916 kW
Total load in tons5.6630 TR

Open this example in the calculator and change any input.

Formula

\(Q_s = \rho\dot V(1006 + 1860W_o)(T_o - T_i), \quad Q_l = \rho\dot V\,h_{fg}(W_o - W_i)\)

Variables

Symbol Meaning SI unit
\(\dot V\) Outdoor air flow m³/s
\(T_o\) Outdoor dry bulb K
\(T_i\) Room dry bulb K
\(W_o\) Outdoor humidity ratio kg/kg
\(W_i\) Room humidity ratio kg/kg
\(Q_s\) Sensible load W
\(Q_l\) Latent load W
\(Q_t\) Total load W
\(Q_{TR}\) Total load in tons W

Method and standards

Outdoor air load.

Where it is used

  • Ventilation design and AHU sizing.
  • Energy recovery evaluation.

Common mistakes

  • Forgetting the latent part.
  • Using room RH instead of humidity ratio.

Assumptions and limits

  • Standard air density; steady state.

References

  • Sensible and latent air-load equations at standard density

Questions and answers

What load does 500 L/s of outdoor air at 35 °C add to a 24 °C room?

About 6.9 kW sensible and 13.1 kW latent at the default humidity: 19.9 kW, near 5.7 TR.

Why is the latent load so large?

Humid outdoor air carries much more water than room air, and removing it takes condensation heat.

What do the defaults represent?

An illustrative 500 L/s of outdoor air at 35 °C and 18 g/kg brought to a room at 24 °C and 9.3 g/kg.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.