Worked example
Example: Illustrative: globe 30 C, air 25 C, 0.3 m/s, 150 mm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Globe temperature | 30.000 °C |
| Air temperature | 25.000 °C |
| Air speed at the globe | 0.30000 m/s |
| Globe diameter (standard 150 mm) | 150.00 mm |
| Globe emissivity (matt black 0.95) | 95.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Mean radiant temperature | 35.302 °C |
| Forced-convection coefficient on the globe | 6.5340 W/(m²·K) |
| Natural-convection coefficient on the globe | 3.3639 W/(m²·K) |
| Operative temperature (mean of air and radiant) | 30.151 °C |
Open this example in the calculator and change any input.
Formula
\(\bar t_r = \left[t_g^4 + \frac{h_{cg}}{\varepsilon_g\sigma}(t_g - t_a)\right]^{1/4}, \quad h_{cg} = \max\left(6.3\frac{v_a^{0.6}}{D^{0.4}},\ 1.4\left(\frac{|t_g - t_a|}{D}\right)^{1/4}\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(t_g\) | Globe temperature | K |
| \(t_a\) | Air temperature | K |
| \(v_a\) | Air speed at the globe | m/s |
| \(D\) | Globe diameter (standard 150 mm) | m |
| \(\varepsilon_g\) | Globe emissivity (matt black 0.95) | - |
| \(\bar t_r\) | Mean radiant temperature | K |
| \(h_{cg,forced}\) | Forced-convection coefficient on the globe | W/(m²·K) |
| \(h_{cg,natural}\) | Natural-convection coefficient on the globe | W/(m²·K) |
| \(t_o\) | Operative temperature (mean of air and radiant) | K |
Method and standards
Globe thermometer heat balance (absolute temperatures).
Where it is used
- Comfort surveys near windows, radiant panels and hot plant.
- Heat-stress assessment.
Common mistakes
- Reading the globe before it has settled.
- Using a small globe without correcting for its diameter.
Assumptions and limits
- Steady state, uniform air speed over the globe.
References
- Globe thermometer heat balance (the ISO 7726 method)
Questions and answers
Why is the globe painted black?
So it absorbs radiation like clothing and skin, which are nearly black in the infrared; its temperature then reflects both air and radiant heat.
Why does air speed matter?
Moving air cools the globe towards the air temperature; without the correction the radiant temperature would be underestimated in draughty spaces.
What do the defaults represent?
An illustrative reading: globe 30 °C, air 25 °C and 0.3 m/s with a standard 150 mm globe.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Parsons, Human Thermal Environments, 3rd ed. (CRC Press, 2014), ch. 5, ASHRAE Handbook – Fundamentals (ASHRAE, 2017), ch. 9 (thermal comfort) and ch. 16 (ventilation and infiltration)