Draught Rate: Percentage Dissatisfied with Local Air Movement

Predicted percentage of people dissatisfied because of draught from the local air temperature, mean air speed and turbulence intensity, by the draught rate model.

Inputs

Examples: Illustrative: 22 C, 0.20 m/s, 40 % turbulenceDisplacement ventilation: 21 C, 0.15 m/s, 15 %Draughty seat near a diffuser: 20 C, 0.35 m/s, 50 %

Accepted: 16 to 26 °C
Accepted: 0 to 0.5 m/s
Accepted: 10 to 70 %

Results

DR = (34 − t)(v − 0.05)^0.62 (0.37 v T_u + 3.14), with v below 0.05 m/s taken as 0.05 and DR capped at 100 %. Applies to people at light, mainly sedentary activity, at neck height.

Draught rate (percentage dissatisfied)12.388%
Air speed giving 20 % draught rate at this temperature and turbulence0.23184m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative: 22 C, 0.20 m/s, 40 % turbulence. The inputs, in the units selected above:

InputValue
Local air temperature22.000 °C
Local mean air speed0.20000 m/s
Turbulence intensity (mixing ventilation 30–60 %)40.000 %

Applying the formula below gives:

ResultValue
Draught rate (percentage dissatisfied)22.578 %
Air speed giving 20 % draught rate at this temperature and turbulence0.18237 m/s

Open this example in the calculator and change any input.

Formula

\(DR = (34 - t_{a,l})(\bar v_{a,l} - 0.05)^{0.62}(0.37\bar v_{a,l}T_u + 3.14)\)

Variables

Symbol Meaning SI unit
\(t_{a,l}\) Local air temperature K
\(\bar v_{a,l}\) Local mean air speed m/s
\(T_u\) Turbulence intensity (mixing ventilation 30–60 %) -
\(DR\) Draught rate (percentage dissatisfied) -
\(v_{DR=20}\) Air speed giving 20 % draught rate at this temperature and turbulence m/s

Method and standards

Draught rate model.

Where it is used

  • Diffuser selection and occupied-zone air speed design.
  • Investigating draught complaints.

Common mistakes

  • Measuring at foot level instead of neck height.
  • Ignoring turbulence intensity in mixing ventilation.

Assumptions and limits

  • Sedentary occupants, 20–26 °C, below 0.5 m/s.

References

  • Fanger's draught rate model (as used in ISO 7730)

Questions and answers

Why does turbulence matter?

Fluctuating air speed is felt more strongly than steady air at the same mean speed; displacement ventilation has low turbulence and allows higher speeds.

What draught rate is acceptable?

Typical comfort categories use about 10, 20 and 30 % for high, normal and moderate expectations.

What do the defaults represent?

An illustrative office position at 22 °C with 0.20 m/s mean air speed and 40 % turbulence intensity.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

ASHRAE Handbook – Fundamentals (ASHRAE, 2017), ch. 9 (thermal comfort) and ch. 16 (ventilation and infiltration), Fanger, Melikov, Hanzawa and Ring, Air turbulence and sensation of draught, Energy and Buildings 12 (1988) 21–39

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.