Worked example
Example: Illustrative 200 m3 room, 1500 to 800 ppm in 1 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Initial CO₂ concentration (ppm) | 1,500.0 - |
| Later CO₂ concentration (ppm) | 800.00 - |
| Outdoor CO₂ concentration (ppm) | 420.00 - |
| Time between readings | 1.0000 h |
| Room volume | 200.00 m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Air change rate | 1.0445 1/h |
| Outdoor air flow | 208.91 m³/h |
| Time to halve the excess CO₂ | 39.815 min |
Open this example in the calculator and change any input.
Formula
\(n = \frac{1}{t}\ln\frac{C_0 - C_o}{C - C_o}, \quad Q = nV\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_0\) | Initial CO₂ concentration (ppm) | - |
| \(C\) | Later CO₂ concentration (ppm) | - |
| \(C_o\) | Outdoor CO₂ concentration (ppm) | - |
| \(t\) | Time between readings | s |
| \(V\) | Room volume | m³ |
| \(n\) | Air change rate | 1/s |
| \(Q\) | Outdoor air flow | m³/s |
| \(t_{1/2}\) | Time to halve the excess CO₂ | s |
Method and standards
Tracer decay.
Where it is used
- Ventilation checks in schools and offices.
- Infiltration testing.
Common mistakes
- Starting while people are still in the room.
- Using indoor background instead of outdoor CO₂.
Assumptions and limits
- Well-mixed room; constant ventilation.
References
- Tracer-gas concentration decay
- Mass balance of a well-mixed room
Questions and answers
Why use CO₂ as a tracer?
Occupants already raise CO₂ well above outdoor levels; logging its fall after they leave measures ventilation without special gases.
What air change rate is typical?
About 0.3–1 per hour in homes and 2–6 per hour in classrooms and offices with mechanical ventilation.
What do the defaults represent?
An illustrative 200 m³ room falling from 1,500 to 800 ppm in one hour, outdoor air at 420 ppm.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.