Air Change Rate from a CO2 Tracer Decay

Air change rate and outdoor air flow of a room from the decay of carbon dioxide concentration towards the outdoor level after occupants leave.

Food, dairy and textile

Inputs

Examples: Illustrative 200 m3 room, 1500 to 800 ppm in 1 hClassroom 2400 to 900 ppm in 30 minLeaky house 1200 to 1000 ppm in 2 h

Accepted: 400 to 20,000
Accepted: 400 to 20,000
Accepted: 300 to 600
Accepted: 0.016667 to 27.778 h
Accepted: 1 to 1,000,000 m³

Results

Well-mixed decay with no sources: C − C_o = (C₀ − C_o)e^(−nt). Use only after occupants leave and with steady ventilation; several readings fitted on a log scale give a better estimate.

Air change rate2.83411/h
Outdoor air flow510.14m³/h
Time to halve the excess CO₂14.674min

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 200 m3 room, 1500 to 800 ppm in 1 h. The inputs, in the units selected above:

InputValue
Initial CO₂ concentration (ppm)1,500.0 -
Later CO₂ concentration (ppm)800.00 -
Outdoor CO₂ concentration (ppm)420.00 -
Time between readings1.0000 h
Room volume200.00 m³

Applying the formula below gives:

ResultValue
Air change rate1.0445 1/h
Outdoor air flow208.91 m³/h
Time to halve the excess CO₂39.815 min

Open this example in the calculator and change any input.

Formula

\(n = \frac{1}{t}\ln\frac{C_0 - C_o}{C - C_o}, \quad Q = nV\)

Variables

Symbol Meaning SI unit
\(C_0\) Initial CO₂ concentration (ppm) -
\(C\) Later CO₂ concentration (ppm) -
\(C_o\) Outdoor CO₂ concentration (ppm) -
\(t\) Time between readings s
\(V\) Room volume m³
\(n\) Air change rate 1/s
\(Q\) Outdoor air flow m³/s
\(t_{1/2}\) Time to halve the excess CO₂ s

Method and standards

Tracer decay.

Where it is used

  • Ventilation checks in schools and offices.
  • Infiltration testing.

Common mistakes

  • Starting while people are still in the room.
  • Using indoor background instead of outdoor CO₂.

Assumptions and limits

  • Well-mixed room; constant ventilation.

References

  • Tracer-gas concentration decay
  • Mass balance of a well-mixed room

Questions and answers

Why use CO₂ as a tracer?

Occupants already raise CO₂ well above outdoor levels; logging its fall after they leave measures ventilation without special gases.

What air change rate is typical?

About 0.3–1 per hour in homes and 2–6 per hour in classrooms and offices with mechanical ventilation.

What do the defaults represent?

An illustrative 200 m³ room falling from 1,500 to 800 ppm in one hour, outdoor air at 420 ppm.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.