Worked example
Example: Illustrative winter attic. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Ceiling U-value | 0.25000 W/(m²·K) |
| Ceiling area | 120.00 m² |
| Roof U-value (attic to outside) | 3.0000 W/(m²·K) |
| Roof area | 140.00 m² |
| Attic ventilation airflow | 180.00 m³/h |
| Indoor temperature | 21.000 °C |
| Outdoor (or roof sol-air) temperature | -5.0000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Attic temperature | -3.4717 °C |
| Heat flow through the ceiling | 734.15 W |
| Heat removed by attic ventilation | 92.250 W |
| Heat lost through the roof | 641.90 W |
Open this example in the calculator and change any input.
Formula
\(T_a = \frac{U_cA_cT_i + (U_rA_r + \rho c_p\dot V)T_o}{U_cA_c + U_rA_r + \rho c_p\dot V}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(U_c\) | Ceiling U-value | W/(m²·K) |
| \(A_c\) | Ceiling area | m² |
| \(U_r\) | Roof U-value (attic to outside) | W/(m²·K) |
| \(A_r\) | Roof area | m² |
| \(\dot V\) | Attic ventilation airflow | m³/s |
| \(T_i\) | Indoor temperature | K |
| \(T_o\) | Outdoor (or roof sol-air) temperature | K |
| \(T_a\) | Attic temperature | K |
| \(Q_c\) | Heat flow through the ceiling | W |
| \(Q_v\) | Heat removed by attic ventilation | W |
| \(Q_r\) | Heat lost through the roof | W |
Method and standards
Attic temperature.
Where it is used
- Heating load of top-floor rooms.
- Unheated garages, crawl spaces and buffer zones.
Common mistakes
- Using outdoor air temperature in summer instead of sol-air.
- Forgetting ventilation.
Assumptions and limits
- Steady state; uniform attic temperature; constant air properties.
References
- Heat balance of an unconditioned space
Questions and answers
Why not use outdoor temperature for the ceiling loss?
The attic acts as a buffer; using its warmer temperature avoids oversizing heating.
What about summer?
Use the roof's sol-air temperature; a hot roof can make the attic much hotter than outdoors.
What do the defaults represent?
An illustrative house: 120 m² ceiling (U 0.25), 140 m² roof (U 3.0), 0.05 m³/s attic ventilation, 21 °C inside and −5 °C outside.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
McQuiston, Parker, Spitler and Taherian, Heating, Ventilating and Air Conditioning, and ASHRAE, Principles of Heating, Ventilating and Air Conditioning, 8th ed. (ASHRAE, 2017)