Adaptive Thermal Comfort Temperature from Outdoor Temperature

Optimum indoor operative temperature and acceptable range for naturally ventilated buildings from the running mean outdoor temperature (adaptive model).

Food, dairy and textile

Inputs

Examples: Illustrative week 17 to 22 C, European formHot spell, ASHRAE formCool spring week

Accepted: -30 to 50 °C
Accepted: -30 to 50 °C
Accepted: -30 to 50 °C
Accepted: -30 to 50 °C
Accepted: -30 to 50 °C
Accepted: -30 to 50 °C
Accepted: -30 to 50 °C
Accepted: 1 to 5 K

Results

Running mean (θ_ed−1 + 0.8θ_ed−2 + 0.6θ_ed−3 + 0.5θ_ed−4 + 0.4θ_ed−5 + 0.3θ_ed−6 + 0.2θ_ed−7)/3.8, used for both forms. For occupants who can open windows and adapt clothing; not for mechanically cooled buildings. Bands of about ±2, ±3 and ±4 K correspond to high, normal and moderate expectation.

Running mean outdoor temperature12.658°C
Optimum comfort temperature22.977°C
Lower acceptable limit20.977°C
Upper acceptable limit24.977°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative week 17 to 22 C, European form. The inputs, in the units selected above:

InputValue
Adaptive modelEuropean form: 0.33·θ_rm + 18.8
Mean outdoor temperature yesterday22.000 °C
Two days ago21.000 °C
Three days ago20.000 °C
Four days ago19.000 °C
Five days ago20.000 °C
Six days ago18.000 °C
Seven days ago17.000 °C
Acceptable band half-width3.0000 K

Applying the formula below gives:

ResultValue
Running mean outdoor temperature20.289 °C
Optimum comfort temperature25.496 °C
Lower acceptable limit22.496 °C
Upper acceptable limit28.496 °C

Open this example in the calculator and change any input.

Formula

\(\theta_{rm} = \frac{\theta_{ed-1} + 0.8\theta_{ed-2} + \dots + 0.2\theta_{ed-7}}{3.8}, \quad \theta_c = 0.33\theta_{rm} + 18.8\)

Variables

Symbol Meaning SI unit
\(\text{model}\) Adaptive model -
\(\theta_{ed-1}\) Mean outdoor temperature yesterday K
\(\theta_{ed-2}\) Two days ago K
\(\theta_{ed-3}\) Three days ago K
\(\theta_{ed-4}\) Four days ago K
\(\theta_{ed-5}\) Five days ago K
\(\theta_{ed-6}\) Six days ago K
\(\theta_{ed-7}\) Seven days ago K
\(\pm\Delta\) Acceptable band half-width K
\(\theta_{rm}\) Running mean outdoor temperature K
\(\theta_c\) Optimum comfort temperature K
\(\theta_{low}\) Lower acceptable limit K
\(\theta_{up}\) Upper acceptable limit K

Method and standards

Adaptive model.

Where it is used

  • Natural ventilation and overheating assessment.
  • Mixed-mode building controls.

Common mistakes

  • Applying it to sealed, air-conditioned buildings.
  • Using monthly instead of running mean temperatures.

Assumptions and limits

  • Sedentary occupants with adaptive opportunities.

References

  • Adaptive comfort model (de Dear and Brager; Nicol and Humphreys)
  • CIBSE Guide A
  • Environmental Design (CIBSE)

Questions and answers

Why does comfort temperature follow the weather?

People in free-running buildings adapt clothing, windows and expectations, so they accept warmer rooms in summer than PMV predicts.

When should I use PMV instead?

In air-conditioned buildings where occupants have little control; there the PMV method applies.

What do the defaults represent?

An illustrative week of daily mean outdoor temperatures from 17 to 22 °C, normal expectation band ±3 K.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.