Wind-Driven Cross Ventilation Flow and Air Changes

Air flow and air change rate of wind-driven cross ventilation through two openings in series from the wind speed, pressure coefficients and opening areas.

Inputs

Examples: Illustrative: 600 m3 room, 1.2 and 1.0 m2 openings, 3.5 m/s, Cp +0.6 / -0.3Warehouse louvres 6 m2 each side, 2 m/s, 4000 m3Small leeward vent limiting flow: 2 m2 and 0.3 m2, 5 m/s

Accepted: 0.01 to 100 m²
Accepted: 0.01 to 100 m²
Accepted: 0.3 to 1
Accepted: 0 to 40 m/s
Accepted: -1.5 to 1.5
Accepted: -1.5 to 1.5
Accepted: 1 to 10,000,000 m³
Accepted: 0.8 to 1.4 kg/m³

Results

Orifice flow through openings in series driven by the wind pressure difference; stack effect, internal partitions and wind turbulence are ignored. Pressure coefficients come from wind tunnel data or tables for the building shape.

Effective opening area (openings in series)4.2426m²
Wind pressure difference ½ρU²ΔC_p2.1600Pa
Air flow17,677m³/h
Air changes per hour4.41941/h
Mean velocity in the windward opening1.3416m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative: 600 m3 room, 1.2 and 1.0 m2 openings, 3.5 m/s, Cp +0.6 / -0.3. The inputs, in the units selected above:

InputValue
Windward opening area1.2000 m²
Leeward opening area1.0000 m²
Discharge coefficient (sharp opening 0.61)0.61000 -
Wind speed at building height3.5000 m/s
Pressure coefficient, windward face0.60000 -
Pressure coefficient, leeward face-0.30000 -
Room or building volume600.00 m³
Air density1.2000 kg/m³

Applying the formula below gives:

ResultValue
Effective opening area (openings in series)0.76822 m²
Wind pressure difference ½ρU²ΔC_p6.6150 Pa
Air flow5,601.5 m³/h
Air changes per hour9.3359 1/h
Mean velocity in the windward opening2.1257 m/s

Open this example in the calculator and change any input.

Formula

\(Q = C_dA_{eff}U\sqrt{\Delta C_p}, \quad \frac{1}{A_{eff}^2} = \frac{1}{A_1^2} + \frac{1}{A_2^2}, \quad n = \frac{Q}{V}\)

Variables

Symbol Meaning SI unit
\(A_1\) Windward opening area m²
\(A_2\) Leeward opening area m²
\(C_d\) Discharge coefficient (sharp opening 0.61) -
\(U\) Wind speed at building height m/s
\(C_{p1}\) Pressure coefficient, windward face -
\(C_{p2}\) Pressure coefficient, leeward face -
\(V\) Room or building volume m³
\(\rho\) Air density kg/m³
\(A_{eff}\) Effective opening area (openings in series) m²
\(\Delta p\) Wind pressure difference ½ρU²ΔC_p Pa
\(Q\) Air flow m³/s
\(n\) Air changes per hour 1/s
\(v_1\) Mean velocity in the windward opening m/s

Method and standards

Wind-driven natural ventilation.

Where it is used

  • Natural ventilation of offices, schools, warehouses and plant rooms.
  • Comparing window and louvre sizes.

Common mistakes

  • Adding opening areas instead of combining them in series.
  • Using the meteorological wind speed without height and terrain correction.

Assumptions and limits

  • Steady wind, sharp-edged openings, no stack effect.

References

  • Wind-driven flow through openings in series (orifice equation)

Questions and answers

Why do the openings combine like resistances in series?

The same air passes through both; the pressure drop splits between them, so the effective area is 1/√(1/A₁² + 1/A₂²), dominated by the smaller opening.

What pressure coefficients are typical?

About +0.5 to +0.8 on a windward wall facing the wind and −0.2 to −0.5 on the leeward wall of a low building.

What do the defaults represent?

An illustrative 600 m³ room with 1.2 m² and 1.0 m² openings on opposite walls, 3.5 m/s wind and C_p of +0.6 and −0.3.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

ASHRAE Handbook – Fundamentals (ASHRAE, 2017), ch. 9 (thermal comfort) and ch. 16 (ventilation and infiltration), CIBSE AM10, Natural Ventilation in Non-Domestic Buildings (CIBSE, 2005)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.