Ventilation Effectiveness and Outdoor Air from CO₂

Contaminant removal effectiveness from supply, exhaust and breathing-zone CO₂, and the outdoor air flow and rate per person from a steady-state CO₂ balance.

Inputs

Examples: Illustrative classroomDisplacement ventilated officeMeeting room, short-circuiting

Accepted: 0 to 10,000 ppm
Accepted: 0 to 50,000 ppm
Accepted: 0 to 50,000 ppm
Accepted: 0.01 to 100,000
Accepted: 1E-4 to 1 L/s

Results

At steady state the CO₂ exhaled by occupants leaves in the exhaust: Q = NG/(C_e − C_s). The contaminant removal effectiveness ε = (C_e − C_s)/(C_b − C_s) compares the exhaust with the breathing zone: 1 for perfect mixing, above 1 for displacement ventilation and below 1 when supply air short-circuits to the exhaust (warm air supplied from the ceiling in heating mode). An adult at office activity exhales about 0.005 L/s of CO₂. CO₂ is a tracer for occupant pollutants, not a toxic hazard at these levels.

Contaminant removal effectiveness0.82759
Outdoor air flow from the exhaust balance325.00L/s
Outdoor air per person10.833L/s
Flow that would give the breathing-zone level with perfect mixing268.97L/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative classroom. The inputs, in the units selected above:

InputValue
Supply air CO₂420.00 ppm
Exhaust (return) air CO₂900.00 ppm
Breathing-zone CO₂1,000.0 ppm
Number of occupants30.000 -
CO₂ generation per person0.005200 L/s

Applying the formula below gives:

ResultValue
Contaminant removal effectiveness0.82759
Outdoor air flow from the exhaust balance325.00 L/s
Outdoor air per person10.833 L/s
Flow that would give the breathing-zone level with perfect mixing268.97 L/s

Open this example in the calculator and change any input.

Formula

\(Q_o = \frac{NG}{C_e - C_s}, \quad \varepsilon_c = \frac{C_e - C_s}{C_b - C_s}\)

Variables

Symbol Meaning SI unit
\(C_s\) Supply air CO₂ -
\(C_e\) Exhaust (return) air CO₂ -
\(C_b\) Breathing-zone CO₂ -
\(N\) Number of occupants -
\(G\) CO₂ generation per person m³/s
\(\varepsilon_c\) Contaminant removal effectiveness -
\(Q_o\) Outdoor air flow from the exhaust balance m³/s
\(q_p\) Outdoor air per person m³/s
\(Q_{o,b}\) Flow that would give the breathing-zone level with perfect mixing m³/s

Method and standards

CO₂ ventilation.

Where it is used

  • Checking ventilation in occupied rooms with CO₂ monitors.
  • Commissioning displacement and mixing systems.

Common mistakes

  • Using readings before CO₂ has reached steady state.
  • Ignoring outdoor CO₂ (about 420 ppm).

Assumptions and limits

  • Steady state; constant occupancy; CO₂ only from occupants.

References

  • Steady-state tracer balance and contaminant removal effectiveness

Questions and answers

Why use exhaust CO₂ for the flow?

All the CO₂ produced must leave in the exhaust, so the exhaust concentration gives the flow whatever the room distribution.

What effectiveness should be expected?

About 1.0 for well-mixed cooling, 0.8 for ceiling-supplied warm air, 1.2 or more for displacement ventilation.

What do the defaults represent?

An illustrative classroom of 30 people with 420 ppm supply, 900 ppm exhaust and 1,000 ppm in the breathing zone.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Etheridge and Sandberg, Building Ventilation: Theory and Measurement (Wiley, 1996)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.