FireCADCalc

Slab-on-Grade Floor Heat Loss (Perimeter Method)

Design heat loss of a slab-on-grade floor from its exposed perimeter and perimeter heat-loss factor, and the annual heating energy from the heating degree-days.

Inputs

Examples: Illustrative house slabInsulated edge, cold climateWarehouse, uninsulated, heat pump

Accepted: 0.05 to 5 W/(m·K)
Accepted: 1 to 10,000 m
Accepted: -3.15 to 36.85 °C
Accepted: -53.15 to 26.85 °C
Accepted: 0 to 10,000
Accepted: 30 to 500 %

Results

Heat from a slab on grade flows mainly out through the edge, so loss is proportional to the exposed perimeter: Q = F_pP(T_i − T_o). F_p depends on the edge insulation and construction (roughly 0.3–0.5 W/m·K with good edge insulation, 1–1.5 W/m·K uninsulated); take it from the design guide for your construction. Annual loss uses the degree-days; ground temperature lag makes this a simplified estimate.

Design heat loss966.00W
Annual heat loss through the slab2,620.8kWh
Annual heating input2,848.7kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative house slab. The inputs, in the units selected above:

InputValue
Perimeter heat-loss factor (W per m per K)0.85000 W/(m·K)
Exposed slab perimeter44.000 m
Indoor design temperature21.000 °C
Outdoor design temperature-10.000 °C
Heating degree-days (K·d)2,800.0 -
Heating system efficiency90.000 %

Applying the formula below gives:

ResultValue
Design heat loss1,159.4 W
Annual heat loss through the slab2,513.3 kWh
Annual heating input2,792.5 kWh

Open this example in the calculator and change any input.

Formula

\(Q = F_pP(T_i - T_o), \quad E = F_pP\cdot HDD\cdot 24\ \text{h}\)

Variables

Symbol Meaning SI unit
\(F_p\) Perimeter heat-loss factor (W per m per K) W/(m·K)
\(P\) Exposed slab perimeter m
\(T_i\) Indoor design temperature K
\(T_o\) Outdoor design temperature K
\(HDD\) Heating degree-days (K·d) -
\(\eta\) Heating system efficiency -
\(Q\) Design heat loss W
\(E\) Annual heat loss through the slab J
\(E_f\) Annual heating input J

Method and standards

Slab heat loss.

Where it is used

  • Heating load of ground-floor rooms.
  • Comparing edge insulation options.

Common mistakes

  • Using floor area with a perimeter factor.
  • Mixing W/m·K and Btu/h·ft·°F factors.

Assumptions and limits

  • Perimeter factor from the design guide; steady state.

References

  • Perimeter heat-loss method

Questions and answers

Why does the loss depend on perimeter, not area?

Deep ground under the middle of a slab is warm; most heat escapes through the short path at the edge.

Does edge insulation matter much?

Yes: it can halve or better the perimeter factor.

What do the defaults represent?

An illustrative house slab with 44 m exposed perimeter and F_p 0.85 W/m·K, 21 °C inside and −10 °C design, 2,800 degree-days.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

McQuiston, Parker, Spitler and Taherian, Heating, Ventilating and Air Conditioning, and ASHRAE, Principles of Heating, Ventilating and Air Conditioning, 8th ed. (ASHRAE, 2017)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.