Radiant Ceiling or Panel Heating and Cooling Capacity

Heat flux and capacity of a radiant panel from its surface temperature, the mean radiant temperature, air temperature, emissivity and convection.

Process steam and utilitiesFood, dairy and textile

Inputs

Examples: Illustrative chilled ceiling 18 CHeated ceiling 35 CRadiant floor cooling 20 C

Accepted: 0 to 100 °C
Accepted: 0 to 56.85 °C
Accepted: 0 to 56.85 °C
Accepted: 5 to 100 %
Accepted: 0.5 to 15 W/(m²·K)
Accepted: 0.1 to 10,000 m²

Results

q_r = εσ(AUST⁴ − T_p⁴), q_c = h_c(T_a − T_p); positive values are heat into the panel (cooling the room), negative values heating. Cooled ceilings reach about 60–100 W/m², limited by the dew point (keep the surface 1–2 K above it); heated ceilings about 100–150 W/m². h_c is small for heated ceilings (about 0.2–1 W/(m²·K)) and larger for cooled ceilings (about 2–3).

Radiant flux (positive: into the panel = cooling)-100.64W/m²
Convective flux-7.5000W/m²
Total flux-108.14W/m²
Panel capacity-4.3258kW
Radiant share93.065%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative chilled ceiling 18 C. The inputs, in the units selected above:

InputValue
Panel surface temperature18.000 °C
Mean temperature of other surfaces26.000 °C
Room air temperature25.000 °C
Panel emissivity90.000 %
Convective coefficient2.5000 W/(m²·K)
Active panel area60.000 m²

Applying the formula below gives:

ResultValue
Radiant flux (positive: into the panel = cooling)41.996 W/m²
Convective flux17.500 W/m²
Total flux59.496 W/m²
Panel capacity3.5698 kW
Radiant share70.586 %

Open this example in the calculator and change any input.

Formula

\(q = \varepsilon\sigma\left(T_{AUST}^4 - T_p^4\right) + h_c(T_a - T_p)\)

Variables

Symbol Meaning SI unit
\(T_p\) Panel surface temperature K
\(T_{AUST}\) Mean temperature of other surfaces K
\(T_a\) Room air temperature K
\(\varepsilon\) Panel emissivity -
\(h_c\) Convective coefficient W/(m²·K)
\(A\) Active panel area m²
\(q_r\) Radiant flux (positive: into the panel = cooling) W/m²
\(q_c\) Convective flux W/m²
\(q\) Total flux W/m²
\(\dot Q\) Panel capacity W
\(q_r/q\) Radiant share -

Method and standards

Radiant panels.

Where it is used

  • Chilled ceiling and radiant floor design.
  • Comfort heating of high spaces.

Common mistakes

  • Ignoring dew point on cooled surfaces.
  • Using a cooled-ceiling h_c for heated ceilings.

Assumptions and limits

  • Panel sees the room as one grey surface at AUST.

References

  • Radiant and convective panel exchange

Questions and answers

What limits a chilled ceiling?

Condensation: the surface must stay above the room dew point, which caps cooling at about 60–100 W/m².

Why are heated ceilings weak in convection?

Warm air stays at the ceiling, so convection from a heated ceiling is small; most output is radiant.

What do the defaults represent?

An illustrative 60 m² chilled ceiling at 18 °C in a 25 °C room with 26 °C surrounding surfaces.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Howell, Sauer and Coad, Principles of Heating, Ventilating and Air Conditioning, 8th ed. (ASHRAE, 2017)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.