Worked example
Example: Illustrative one-storey house. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Effective leakage area at 4 Pa (cm²) | 500.00 - |
| Stack coefficient (L/s)²/(cm⁴·K) | 1.4500e-04 - |
| Wind coefficient (L/s)²/(cm⁴·(m/s)²) | 1.0400e-04 - |
| Indoor temperature | 21.000 °C |
| Outdoor temperature | -5.0000 °C |
| Wind speed at the weather station | 16.200 km/h |
| Building volume | 400.00 m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Stack-only infiltration | 30.700 L/s |
| Wind-only infiltration | 22.946 L/s |
| Combined infiltration | 38.328 L/s |
| Air changes per hour | 0.34495 |
| Sensible heat loss | 1.3197 kW |
Open this example in the calculator and change any input.
Formula
\(Q = A_L\sqrt{C_s\Delta T + C_wU^2}, \quad ACH = \frac{3600\,Q}{V}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A_L\) | Effective leakage area at 4 Pa (cm²) | - |
| \(C_s\) | Stack coefficient (L/s)²/(cm⁴·K) | - |
| \(C_w\) | Wind coefficient (L/s)²/(cm⁴·(m/s)²) | - |
| \(T_i\) | Indoor temperature | K |
| \(T_o\) | Outdoor temperature | K |
| \(U\) | Wind speed at the weather station | m/s |
| \(V\) | Building volume | m³ |
| \(Q_s\) | Stack-only infiltration | m³/s |
| \(Q_w\) | Wind-only infiltration | m³/s |
| \(Q\) | Combined infiltration | m³/s |
| \(ACH\) | Air changes per hour | - |
| \(\dot Q_h\) | Sensible heat loss | W |
Method and standards
Combined infiltration.
Where it is used
- Heating load infiltration allowance.
- Assessing airtightness improvements.
Common mistakes
- Using leakage area at 10 Pa (EqLA) with 4 Pa coefficients.
- Using wind at roof height instead of the weather station.
Assumptions and limits
- Single zone; coefficients for the building's height and shelter.
References
- Effective leakage area infiltration model
Questions and answers
Where does the leakage area come from?
A blower-door test, reporting effective leakage area at 4 Pa (ELA) or from n50 via a conversion.
Why add stack and wind in quadrature?
They act on the same openings with partly opposing pressure patterns; the root-sum-square fits measurements well.
What do the defaults represent?
An illustrative one-storey 400 m³ house with 500 cm² leakage area, 21 °C inside, −5 °C outside, 4.5 m/s wind.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Sherman and Grimsrud, Infiltration-Pressurization Correlation: Simplified Physical Modeling, ASHRAE Transactions 86 (1980)