FireCADCalc

Blower Door Test: ACH50, Air Permeability and Leakage Area

Air changes at 50 Pa, air permeability, an estimate of natural air change rate and the equivalent leakage area at 4 Pa from a blower door test result.

Food, dairy and textile

Inputs

Examples: Illustrative 400 m3 house, 1500 m3/h at 50 PaVery tight houseLeaky old house

Accepted: 3.6 to 360,000 m³/h
Accepted: 10 to 1,000,000 m³
Accepted: 10 to 1,000,000 m²
Accepted: 0.5 to 1
Accepted: 5 to 40
Accepted: 0.9 to 1.4 kg/m³

Results

Q = C·Δpⁿ scales the 50 Pa flow to 4 Pa; ELA = Q₄√(ρ/2Δp) (discharge coefficient 1). The divisor N (about 10–30) depends on climate, height and shielding; it gives only a rough seasonal average infiltration.

Air changes at 50 Pa0.600001/h
Air permeability0.72727m³/(h·m²)
Estimated natural air change rate0.0300001/h
Leakage at 4 Pa52.731m³/h
Equivalent leakage area at 4 Pa56.729cm²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 400 m3 house, 1500 m3/h at 50 Pa. The inputs, in the units selected above:

InputValue
Leakage flow at 50 Pa1,500.0 m³/h
Building internal volume400.00 m³
Envelope area330.00 m²
Flow exponent0.65000 -
ACH50 to natural ACH divisor20.000 -
Air density1.2000 kg/m³

Applying the formula below gives:

ResultValue
Air changes at 50 Pa3.7500 1/h
Air permeability4.5455 m³/(h·m²)
Estimated natural air change rate0.18750 1/h
Leakage at 4 Pa290.47 m³/h
Equivalent leakage area at 4 Pa312.49 cm²

Open this example in the calculator and change any input.

Formula

\(n_{50} = \frac{\dot V_{50}}{V}, \quad \dot V_4 = \dot V_{50}\left(\frac{4}{50}\right)^n, \quad ELA = \dot V_4\sqrt{\frac{\rho}{2\cdot4\,\mathrm{Pa}}}\)

Variables

Symbol Meaning SI unit
\(\dot V_{50}\) Leakage flow at 50 Pa m³/s
\(V\) Building internal volume m³
\(A_E\) Envelope area m²
\(n\) Flow exponent -
\(N\) ACH50 to natural ACH divisor -
\(\rho\) Air density kg/m³
\(n_{50}\) Air changes at 50 Pa 1/s
\(q_{50}\) Air permeability m/s
\(n_{nat}\) Estimated natural air change rate 1/s
\(\dot V_4\) Leakage at 4 Pa m³/s
\(ELA_4\) Equivalent leakage area at 4 Pa m²

Method and standards

Pressurisation test.

Where it is used

  • Energy rating and building regulations checks.
  • Ventilation design for tight houses.

Common mistakes

  • Comparing ACH50 between very different building sizes.
  • Treating ACH50 as natural infiltration.

Assumptions and limits

  • Power-law leakage; single-zone building.

References

  • Fan pressurisation test interpretation
  • ASHRAE Handbook of Fundamentals (ASHRAE)
  • ch. 16

Questions and answers

What ACH50 is good?

About 3 or below for new efficient homes, under 1 for very tight (Passivhaus-level 0.6) houses; old houses often exceed 10.

Is ACH50 the real infiltration?

No: it is measured at 50 Pa; natural infiltration is roughly ACH50 divided by 10–30.

What do the defaults represent?

An illustrative 400 m³ house leaking 1,500 m³/h at 50 Pa with 330 m² of envelope, flow exponent 0.65.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.