FireCADCalc

Quick Air Conditioner Size for a Room

Rough cooling capacity for a room from floor area and a fabric-and-sun load per m², occupants, lighting and equipment, in kW, tons of refrigeration and BTU/h.

Food, dairy and textile

Inputs

Examples: Illustrative 25 m2 sunny roomSmall office 60 m2, 8 peopleShaded bedroom 14 m2

Accepted: 1 to 100,000 m²
Accepted: 0.01 to 0.5 kW/m²
Accepted: 0 to 10,000
Accepted: 0.05 to 0.3 kW
Accepted: 0 to 0.3 kW
Accepted: 0 to 0.05 kW/m²
Accepted: 0 to 1,000 kW
Accepted: 1 to 1.5

Results

Rule-of-thumb sizing: fabric and solar load per m² (about 60–80 W/m² for shaded rooms in mild climates, 120–180 W/m² for sunny rooms in hot climates) plus people, lights and equipment. Use a proper heat-gain calculation for anything beyond a single room.

Sensible load7.6000kW
Latent load0.44000kW
Cooling capacity to select8.8440kW
Capacity in tons of refrigeration2.5147TR
Capacity in BTU/h30,177Btu/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 25 m2 sunny room. The inputs, in the units selected above:

InputValue
Floor area25.000 m²
Fabric and solar load per m² of floor0.10000 kW/m²
Occupants3.0000 -
Sensible heat per person0.075000 kW
Latent heat per person0.055000 kW
Lighting per m²0.008000 kW/m²
Equipment heat0.40000 kW
Safety factor1.1000 -

Applying the formula below gives:

ResultValue
Sensible load3.3250 kW
Latent load0.16500 kW
Cooling capacity to select3.8390 kW
Capacity in tons of refrigeration1.0916 TR
Capacity in BTU/h13,099 Btu/h

Open this example in the calculator and change any input.

Formula

\(Q = k\left[A(q_A + q_{lt}) + N(q_s + q_l) + Q_{eq}\right]\)

Variables

Symbol Meaning SI unit
\(A\) Floor area m²
\(q_A\) Fabric and solar load per m² of floor W/m²
\(N\) Occupants -
\(q_s\) Sensible heat per person W
\(q_l\) Latent heat per person W
\(q_{lt}\) Lighting per m² W/m²
\(Q_{eq}\) Equipment heat W
\(k\) Safety factor -
\(Q_s\) Sensible load W
\(Q_l\) Latent load W
\(Q\) Cooling capacity to select W

Method and standards

Quick sizing.

Where it is used

  • Room and small-office split units.
  • Sanity checks of quotations.

Common mistakes

  • Ignoring people and equipment.
  • Oversizing heavily, which harms dehumidification.

Assumptions and limits

  • Rule-of-thumb loads; single room.

References

  • Room cooling load by unit-area allowance
  • ASHRAE Handbook of Fundamentals (ASHRAE)

Questions and answers

How many tons for a 25 m² room?

About 1 ton (3.5 kW) for a sunny room with a few people by these allowances; shaded rooms need less.

Why not just use W/m²?

People and equipment can double the load in small offices or kitchens; add them separately.

What do the defaults represent?

An illustrative 25 m² room with 100 W/m² fabric and sun load, three people, 8 W/m² lighting and 400 W of equipment, safety factor 1.1.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.