Worked example
Example: Indian coal boiler. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gross calorific value of the fuel | 17,500 kJ/kg |
| Flue gas temperature at the stack | 140.00 °C |
| Combustion air temperature | 30.000 °C |
| Dry flue gas per kg fuel | 7.4700 kg/kg |
| Dry air per kg fuel | 6.5600 kg/kg |
| Hydrogen in fuel, as fired | 3.5000 % |
| Moisture in fuel, as fired | 10.000 % |
| Air humidity (kg water per kg dry air) | 0.013000 kg/kg |
| CO₂ in dry flue gas | 14.500 % |
| O₂ in dry flue gas | 4.5000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Dry gas loss | 827.72 kJ/kg |
| Water from hydrogen loss | 825.17 kJ/kg |
| Fuel moisture loss | 263.83 kJ/kg |
| Air moisture loss | 17.681 kJ/kg |
| Total stack loss | 1,934.4 kJ/kg |
| Dry gas loss | 4.7298 % |
| Water from hydrogen loss | 4.7152 % |
| Fuel moisture loss | 1.5076 % |
| Air moisture loss | 0.10103 % |
| Total stack loss | 11.054 % |
| Mean specific heat of dry gas, air to stack temperature | 1.0073 kJ/(kg·K) |
Open this example in the calculator and change any input.
Formula
\(Q_{dg} = m_{g,dry}\left[h_g(T_g) - h_g(T_a)\right] \qquad Q_{H} = \frac{M_{H_2O}}{M_{H_2}}\,H\left[h_v(T_g) - h_f(T_a)\right] \qquad Q_{M} = M\left[h_v(T_g) - h_f(T_a)\right] \qquad Q_{\omega} = \omega\,m_a\left[h_v(T_g) - h_v(T_a)\right]\)
\(Q_{st} = Q_{dg} + Q_{H} + Q_{M} + Q_{\omega} \qquad L_i = \frac{Q_i}{GCV} \qquad \bar c_{p,g} = \frac{h_g(T_g) - h_g(T_a)}{T_g - T_a}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(GCV\) | gross calorific value of the fuel as fired | J/kg |
| \(T_g\) | flue gas temperature at the stack | K |
| \(T_a\) | combustion air temperature (reference for the losses) | K |
| \(m_{g,dry}\) | dry flue gas per kg fuel | kg/kg |
| \(m_{a}\) | dry combustion air per kg fuel | kg/kg |
| \(H\) | hydrogen in the fuel as fired, mass fraction | – |
| \(M\) | moisture in the fuel as fired, mass fraction | – |
| \(\omega\) | air humidity, kg water per kg dry air | kg/kg |
| \(y_{CO_2}\), \(y_{O_2}\) | CO₂ and O₂ in the dry flue gas, volume fractions (N₂ + Ar by difference) | – |
| \(h_g\) | enthalpy of the dry flue gas (Shomate integration over the entered composition) | J/kg |
| \(h_v\) | enthalpy of water vapour: IF97 at 1 psia for the water from hydrogen and fuel moisture; ideal-gas (Shomate) H₂O for the moisture in the air | J/kg |
| \(h_f\) | enthalpy of saturated liquid water at \(T_a\) (IF97) | J/kg |
| \(M_{H_2O}/M_{H_2}\) | water formed per kg hydrogen, 8.936 | kg/kg |
| \(Q_{dg}\), \(Q_{H}\), \(Q_{M}\), \(Q_{\omega}\), \(Q_{st}\) | losses per kg fuel: dry gas, water from hydrogen, fuel moisture, air moisture, total | J/kg |
| \(L_{dg}\), \(L_{H}\), \(L_{M}\), \(L_{\omega}\), \(L_{st}\) | the same as fractions of GCV | – |
| \(\bar c_{p,g}\) | mean specific heat of the dry flue gas between \(T_a\) and \(T_g\) | J/(kg·K) |
Method and standards
The loss definitions of ASME PTC 4 §5.14 applied with the combustion air temperature as the reference, which is the form used by the BS 845 / IS 8753 audit methods. Dry gas enthalpy is integrated from NIST Shomate heat capacities of the entered CO₂/O₂/N₂ composition instead of a constant 1.005 kJ/(kg·K); the water terms use IF97 enthalpies of vapour at 1 psia and of liquid at the air temperature, which is what the latent-heat-plus-superheat approximation (2 442 + 1.88 ΔT) stands in for.
Where it is used
- Quick stack loss checks during combustion tuning.
- Energy audits with a portable flue gas analyser.
- Comparing O₂ and stack temperature effects.
Common mistakes
- Using flue gas temperature at the stack instead of at the boiler exit.
- Mixing wet and dry O₂ readings.
- Taking stack loss as the whole loss: radiation, unburned carbon and CO are extra.
Assumptions and limits
- Argon and SO₂ in the dry gas are lumped into N₂ (error below 0.2 % of the dry gas loss).
- Complete combustion; CO, unburned carbon, radiation and residue losses are not included here; use the boiler efficiency calculator for the full balance.
- Stack temperature above about 39 °C (water vapour at 1 psia).
- The dry gas mass, dry air mass and dry gas CO₂ and O₂ are independent inputs and are not checked against each other; take all of them from the same combustion calculation at the measured excess air, or the dry gas loss matches neither condition.
References
- ASME PTC 4-2013 §5.14.2–5.14.4 (loss definitions)
- NIST-JANAF Shomate heat capacities
- IAPWS-IF97
Questions and answers
What is the rule of thumb for the dry gas loss?
About 1 % of input for every 20 K of stack temperature above the air temperature at normal excess air, which this calculator reproduces: 12.5 kg of dry gas at a mean cp of 1.02 kJ/(kg·K) over 120 K is 1.53 MJ, or 7.7 % of a 20 MJ/kg coal.
Why is the reference here the air temperature and not 25 °C?
This is the quick stack-loss form, which many audit methods (BS 845, IS 8753) use: losses counted from the air temperature with no separate credits. The full PTC 4 calculator references to 25 °C and adds credits; for air at 25 °C the two agree.
Which dry gas quantity do I enter?
The dry flue gas mass per kg fuel from the combustion calculator at the measured excess air, or a measured flue gas flow divided by the fuel flow and corrected for moisture.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.