Worked example
Example: Baffled contact tank: 20,000 m3/d, 2 m wide, 4 m deep, 300 m path. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flow | 20,000 m³/d |
| Channel width | 2.0000 m |
| Water depth | 4.0000 m |
| Channel length (flow path) | 300.00 m |
| Kinematic viscosity | 1.3100e-06 m²/s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Mean velocity | 0.028935 m/s |
| Hydraulic radius | 0.80000 m |
| Reynolds number (4vR_h/ν) | 70,681 |
| Longitudinal dispersion coefficient | 0.023160 m²/s |
| Dispersion number E/(vL) | 0.002668 |
| Mean hydraulic residence time | 172.80 min |
Open this example in the calculator and change any input.
Formula
\(Re = \frac{4vR_h}{\nu}, \quad E = 1.01\nu Re^{0.875}, \quad d = \frac{E}{vL}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Flow | m³/s |
| \(W\) | Channel width | m |
| \(h\) | Water depth | m |
| \(L\) | Channel length (flow path) | m |
| \(\nu\) | Kinematic viscosity | m²/s |
| \(v\) | Mean velocity | m/s |
| \(R_h\) | Hydraulic radius | m |
| \(Re\) | Reynolds number (4vR_h/ν) | - |
| \(E\) | Longitudinal dispersion coefficient | m²/s |
| \(d\) | Dispersion number E/(vL) | - |
| \(\tau\) | Mean hydraulic residence time | s |
Method and standards
Empirical longitudinal dispersion in open channels.
Where it is used
- Contact tank and channel design for CT credit.
- Interpreting tracer tests.
Common mistakes
- Using the depth instead of the hydraulic radius.
- Comparing d from tracer tests with a different definition.
Assumptions and limits
- Turbulent, uniform channel flow.
Questions and answers
Why does dispersion matter for disinfection?
Credit is given on T10, the time for 10 % of a tracer to pass; low dispersion makes T10 close to the mean time.
How do I reduce d?
Increase the length-to-width ratio of the flow path with baffles; ratios above 40:1 approach plug flow.
What do the defaults represent?
An illustrative case: Baffled contact tank: 20,000 m3/d, 2 m wide, 4 m deep, 300 m path. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 6-7, eq. 6-113 and Example 6-6