Worked example
Example: Illustrative 150 mm borewell, 5 % bleach. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Well or casing inside diameter | 150.00 mm |
| Depth of water in the well | 40.000 m |
| Chlorine concentration wanted | 100.00 mg/L |
| Available chlorine in the product | 5.0000 % |
| Product density (liquids) | 1,070.0 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Water volume | 706.86 L |
| Chlorine needed | 70.686 g |
| Product mass | 1.4137 kg |
| Product volume (liquids) | 1.3212 L |
Open this example in the calculator and change any input.
Formula
\(V = \frac{\pi d^2}{4}h, \quad m_{Cl} = cV, \quad m_p = \frac{m_{Cl}}{s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(d\) | Well or casing inside diameter | m |
| \(h\) | Depth of water in the well | m |
| \(c\) | Chlorine concentration wanted | kg/m³ |
| \(s\) | Available chlorine in the product | - |
| \(\rho\) | Product density (liquids) | kg/m³ |
| \(V\) | Water volume | m³ |
| \(m_{Cl}\) | Chlorine needed | kg |
| \(m_p\) | Product mass | kg |
| \(V_p\) | Product volume (liquids) | m³ |
Method and standards
Well chlorination.
Where it is used
- Rural water supply and borewells.
- Disinfection after repairs or floods.
Common mistakes
- Forgetting pipework volume.
- Using old, weakened bleach.
Assumptions and limits
- Uniform mixing in the well.
References
- Volume and dose arithmetic for shock disinfection
Questions and answers
How much bleach for a 150 mm borewell with 40 m of water at 100 mg/L?
The well holds about 707 litres; about 1.3 litres of 5 % bleach.
How long should chlorine stay in the well?
Typically 12 to 24 hours before flushing and testing.
What do the defaults represent?
An illustrative 150 mm borewell with 40 m of water, disinfected at 100 mg/L with 5 % bleach.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.