FireCADCalc

Rectangular Sedimentation Basin: Size, Detention, Reynolds and Froude

Surface area and length from overflow rate, detention time, horizontal velocity and the Reynolds and Froude number checks of a rectangular sedimentation basin.

Inputs

Examples: Small plant 0.2 m3/s, 1.5 m/h, two 8 x 3.5 m basins, 20 C

Accepted: 0.001 to 100 m³/s
Accepted: 0.001 to 100 m³/s
Accepted: 0.036 to 36 m/h
Accepted: 1 to 50
Accepted: 1 to 100 m
Accepted: 1 to 10 m
Accepted: 1 to 10
Accepted: 0.1 to 5 mPa·s
Accepted: 900 to 1,100 kg/m³

Results

Guidance: L/W at least 4–5, L/h at least 15, detention 1.5–4 h, horizontal velocity 0.3–1.1 m/min, Re below 20,000 and Fr above 10⁻⁵.

Fr is below 10⁻⁵: the flow is prone to density currents; narrower channels help.

Total surface area480.00m²
Basin length30.000m
Length to width ratio3.7500
Length to depth ratio8.5714
Detention time at design flow2.3333h
Detention time at average flow3.1111h
Horizontal velocity0.21429m/min
Hydraulic radius of a channel1.8667m
Reynolds number (keep below 20,000)6,654.7
Froude number (keep above 10⁻⁵)6.9678e-07

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Small plant 0.2 m3/s, 1.5 m/h, two 8 x 3.5 m basins, 20 C. The inputs, in the units selected above:

InputValue
Design (maximum day) flow0.20000 m³/s
Average flow0.15000 m³/s
Overflow rate (critical settling velocity)1.5000 m/h
Number of basins2.0000 -
Basin width8.0000 m
Water depth3.5000 m
Flow channels per basin (longitudinal baffles + 1)1.0000 -
Water dynamic viscosity (10 °C 1.31 mPa·s, 20 °C 1.00)1.0000 mPa·s
Water density998.20 kg/m³

Applying the formula below gives:

ResultValue
Total surface area480.00 m²
Basin length30.000 m
Length to width ratio3.7500
Length to depth ratio8.5714
Detention time at design flow2.3333 h
Detention time at average flow3.1111 h
Horizontal velocity0.21429 m/min
Hydraulic radius of a channel1.8667 m
Reynolds number (keep below 20,000)6,654.7
Froude number (keep above 10⁻⁵)6.9678e-07

Open this example in the calculator and change any input.

Formula

\(A = \frac{Q}{v_c}, \quad L = \frac{A}{n_bW}, \quad v_f = \frac{Q}{n_bWh}\)

\(R_h = \frac{(W/n_c)h}{W/n_c + 2h}, \quad Re = \frac{\rho v_fR_h}{\mu}, \quad Fr = \frac{v_f^2}{gR_h}\)

Variables

Symbol Meaning SI unit
\(Q\) Design (maximum day) flow m³/s
\(Q_{avg}\) Average flow m³/s
\(v_c\) Overflow rate (critical settling velocity) m/s
\(n_b\) Number of basins -
\(W\) Basin width m
\(h\) Water depth m
\(n_c\) Flow channels per basin (longitudinal baffles + 1) -
\(\mu\) Water dynamic viscosity (10 °C 1.31 mPa·s, 20 °C 1.00) Pa·s
\(\rho\) Water density kg/m³
\(A\) Total surface area m²
\(L\) Basin length m
\(L/W\) Length to width ratio -
\(L/h\) Length to depth ratio -
\(t_d\) Detention time at design flow s
\(t_{avg}\) Detention time at average flow s
\(v_f\) Horizontal velocity m/s
\(R_h\) Hydraulic radius of a channel m
\(Re\) Reynolds number (keep below 20,000) -
\(Fr\) Froude number (keep above 10⁻⁵) -

Method and standards

Ideal-basin overflow rate design with hydraulic stability checks.

Where it is used

  • Sizing conventional sedimentation for a new plant.
  • Checking existing basins at a new capacity.

Common mistakes

  • Designing on average flow.
  • Ignoring the Froude criterion in wide, shallow basins.

Assumptions and limits

  • Ideal settling at the overflow rate; even flow distribution.

Questions and answers

Why check the Froude number?

A very low Froude number means inertia is weak against gravity, so temperature or density differences can short-circuit the basin; narrower channels raise it.

Why design on the maximum day flow?

The basin must still settle the floc on the worst day; at average flow the detention is longer and performance better.

What do the defaults represent?

An illustrative case: Small plant 0.2 m3/s, 1.5 m/h, two 8 x 3.5 m basins, 20 C. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 10-6, eqs. 10-17, 10-32 and 10-33, Table 10-4 and Example 10-6

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.