Worked example
Example: Cryptosporidium challenge 2e6 in, detection limit 1 out. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Feed concentration (any consistent unit) | 2,000,000 - |
| Permeate concentration (same unit) | 1.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Rejection | 100.000 % |
| Log removal value | 6.3010 |
| Passage | 5.0000e-07 |
Open this example in the calculator and change any input.
Formula
\(R = 1 - \frac{C_p}{C_f}, \quad LRV = \log_{10}\frac{C_f}{C_p}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_f\) | Feed concentration (any consistent unit) | - |
| \(C_p\) | Permeate concentration (same unit) | - |
| \(R\) | Rejection | - |
| \(LRV\) | Log removal value | - |
| \(C_p/C_f\) | Passage | - |
Method and standards
Definitions of rejection and log removal.
Where it is used
- Membrane integrity and challenge testing.
- Pathogen credit accounting across treatment barriers.
Common mistakes
- Using natural logarithms.
- Mixing units between feed and permeate.
Assumptions and limits
- Concentrations measured on the same basis and sample timing.
Questions and answers
Why use LRV instead of percent?
Pathogen removal spans many orders of magnitude; 99.9999 % and 99.99987 % look alike but are 6.0 and 5.9 log.
Can LRVs be added?
For independent barriers in series, yes: credits from filtration and disinfection add up toward the regulatory requirement.
What do the defaults represent?
An illustrative case: Cryptosporidium challenge 2e6 in, detection limit 1 out. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 12-4, eqs. 12-3 and 12-4 and Example 12-2