Worked example
Example: Low-NOM groundwater: DOC 1 mg/L, UV 0.02, bromide 0.2 mg/L. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Dissolved organic carbon | 1.0000 mg/L |
| UV254 absorbance, 1/cm | 0.020000 - |
| Bromide | 0.20000 mg/L |
| Water temperature, °C (Obolensky–Singer) | 15.000 - |
| Alkalinity, mg/L as CaCO₃ | 200.00 - |
| Chlorine consumed (dose − residual), mg/L | 1.0000 - |
| Chlorine contact time | 2.0000 h |
| pH | 7.8000 - |
| Chlorine residual in finished water, mg/L | 0.80000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Specific UV absorbance, L/(mg·m) | 2.0000 |
| THM formation potential | 46.859 µg/L |
| HAA formation potential | 31.731 µg/L |
| THM4 under plant conditions, µmol/L | 0.079136 |
| THM4 expressed as chloroform | 9.4473 µg/L |
Open this example in the calculator and change any input.
Formula
\(THMFP_4 = 1147\,(UV)^{0.83}(Br + 1)^{0.27}, \quad HAAFP_9 = 1151\,(DOC)^{0.17}(UV)^{0.89}(Br + 1)^{-0.60}\)
\(\log[THM_4] = -1.371 + 0.015T - 0.0005ALK + 0.188\log TOC + 0.326\log UV + 0.291\log Cl_2 + 0.119\log t + 0.087pH + 0.167\log Cl_{res}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(DOC\) | Dissolved organic carbon | kg/m³ |
| \(UV_{254}\) | UV254 absorbance, 1/cm | - |
| \(Br^-\) | Bromide | kg/m³ |
| \(T\) | Water temperature, °C (Obolensky–Singer) | - |
| \(ALK\) | Alkalinity, mg/L as CaCO₃ | - |
| \(Cl_2\) | Chlorine consumed (dose − residual), mg/L | - |
| \(t\) | Chlorine contact time | s |
| \(pH\) | pH | - |
| \(Cl_{res}\) | Chlorine residual in finished water, mg/L | - |
| \(SUVA\) | Specific UV absorbance, L/(mg·m) | - |
| \(THMFP_4\) | THM formation potential | kg/m³ |
| \(HAAFP_9\) | HAA formation potential | kg/m³ |
| \([THM_4]\) | THM4 under plant conditions, µmol/L | - |
| \(THM_4\,(as\ CHCl_3)\) | THM4 expressed as chloroform | kg/m³ |
Method and standards
Empirical regressions for chlorination by-product formation.
Where it is used
- Screening sources and treatment for DBP compliance.
- Judging the benefit of NOM removal before chlorination.
Common mistakes
- Treating formation potential as the distribution-system value.
- Mixing units (bromide in mg/L, UV in 1/cm).
Assumptions and limits
- Within the data ranges of the regressions; free chlorine only.
Questions and answers
What does SUVA tell me?
UV254 per unit DOC: above about 4 L/(mg·m) the NOM is mostly humic and hydrophobic, forms more DBPs and responds well to enhanced coagulation; below 2 it is mostly non-humic.
Why does bromide raise THMs but lower HAA9 here?
Bromide shifts formation to brominated species, which weigh more per mole (raising THM mass), while the fitted HAA9 relation falls with bromide.
What do the defaults represent?
An illustrative case: Low-NOM groundwater: DOC 1 mg/L, UV 0.02, bromide 0.2 mg/L. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 19-2, eqs. 19-4 to 19-6 and Example 19-3 (Obolensky and Singer 2008; Chen and Westerhoff 2010)