Worked example
Example: Within the lag: 0.48 mg/L for 61.6 min. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Coefficient of specific lethality, L/(mg·min) | 0.083000 - |
| Lag coefficient, mg·min/L | 34.900 - |
| Disinfectant concentration | 0.48000 mg/L |
| Contact time | 61.600 min |
| Target log inactivation | 1.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Ct provided, mg·min/L | 29.568 |
| Log inactivation achieved | 0 |
| Ct needed for the target, mg·min/L | 62.642 |
| Contact time needed at C | 130.50 min |
Open this example in the calculator and change any input.
Formula
\(\ln\frac{N}{N_0} = \begin{cases}0 & Ct < b\\ -\Lambda_{CW}(Ct - b) & Ct \ge b\end{cases}\)
\(Ct_{req} = b + \frac{2.303\,\log_{10}(N_0/N)}{\Lambda_{CW}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\Lambda_{CW}\) | Coefficient of specific lethality, L/(mg·min) | - |
| \(b\) | Lag coefficient, mg·min/L | - |
| \(C\) | Disinfectant concentration | kg/m³ |
| \(t\) | Contact time | s |
| \(\log_{10}(N_0/N)\) | Target log inactivation | - |
| \(Ct\) | Ct provided, mg·min/L | - |
| \(Ct_{req}\) | Ct needed for the target, mg·min/L | - |
| \(t_{req}\) | Contact time needed at C | s |
Method and standards
Chick–Watson inactivation delayed by a lag Ct.
Where it is used
- Cryptosporidium and Giardia credit with ClO₂ and ozone.
- Spore and oocyst inactivation studies.
Common mistakes
- Applying a first-order Chick–Watson fit to lagging data.
- Forgetting temperature: Λ and b change with it.
Assumptions and limits
- Constant C and temperature; parameters from bench tests.
Questions and answers
Why is there a lag?
Resistant organisms such as Cryptosporidium oocysts and spores need several hits before they die, so nothing happens until a threshold Ct is passed.
How do I get Λ and b?
Fit log survival against Ct: the line's intercept on the Ct axis is b and its slope (×2.303) is Λ_CW.
What do the defaults represent?
An illustrative case: Within the lag: 0.48 mg/L for 61.6 min. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 13-3, eqs. 13-5 and 13-6 and Example 13-2 (Rennecker et al. 1997; Corona-Vasquez et al. 2002)