FireCADCalc

Vertical Turbine Flocculator: Stage Volume, Power, Speed and G

Stage volume and size, water power for a velocity gradient G, impeller speed from the power number, pumping rate and circulation time of a turbine flocculator.

Inputs

Examples: Third stage of the same train at G 40Small plant 5 ML/d, 2 x 3 stages, 30 min, G 60, 0.9 m pitched blade Np 1.3, 20 C

Accepted: 8.64 to 8,640,000 m³/d
Accepted: 1 to 20
Accepted: 1 to 10
Accepted: 1 to 600 min
Accepted: 5 to 200 1/s
Accepted: 0.1 to 10 m
Accepted: 0.05 to 10
Accepted: 0.1 to 2
Accepted: 0.1 to 5 mPa·s
Accepted: 900 to 1,100 kg/m³

Results

A cubic stage is assumed for the size. Typical practice: G 80–100 s⁻¹ in the first stage tapering to 20–40 s⁻¹, total Gt 10⁴–10⁵, speed 10–30 rpm, tip speed below about 2–3 m/s.

Stage volume65.104m³
Side of a cubic stage4.0229m
Equivalent tank diameter4.5393m
Suggested impeller diameter2.0427m
Water power136.46W
Impeller speed15.447rpm
Tip speed1.6176m/s
Impeller pumping rate1.0298m³/s
Circulation time63.222s
Gt for this stage12,000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Third stage of the same train at G 40. The inputs, in the units selected above:

InputValue
Plant flow75,000 m³/d
Parallel trains4.0000 -
Stages in series per train4.0000 -
Total flocculation time20.000 min
Velocity gradient in this stage40.000 1/s
Impeller diameter (about 0.45 of the equivalent tank diameter)2.0000 m
Impeller power number (pitched foil 0.2–0.3, pitched blade 1.3)0.25000 -
Impeller pumping number (foil about 0.5)0.50000 -
Water dynamic viscosity (10 °C 1.31 mPa·s, 20 °C 1.00)1.3100 mPa·s
Water density999.70 kg/m³

Applying the formula below gives:

ResultValue
Stage volume65.104 m³
Side of a cubic stage4.0229 m
Equivalent tank diameter4.5393 m
Suggested impeller diameter2.0427 m
Water power136.46 W
Impeller speed15.447 rpm
Tip speed1.6176 m/s
Impeller pumping rate1.0298 m³/s
Circulation time63.222 s
Gt for this stage12,000

Open this example in the calculator and change any input.

Formula

\(P = G^2\mu V, \quad N = \left(\frac{P}{N_p\rho D^5}\right)^{1/3}\)

\(Q_p = N_QND^3, \quad t_c = \frac{V}{Q_p}, \quad T_e = \sqrt{\frac{4A_{plan}}{\pi}}\)

Variables

Symbol Meaning SI unit
\(Q\) Plant flow m³/s
\(n_t\) Parallel trains -
\(n_s\) Stages in series per train -
\(t\) Total flocculation time s
\(G\) Velocity gradient in this stage 1/s
\(D\) Impeller diameter (about 0.45 of the equivalent tank diameter) m
\(N_p\) Impeller power number (pitched foil 0.2–0.3, pitched blade 1.3) -
\(N_Q\) Impeller pumping number (foil about 0.5) -
\(\mu\) Water dynamic viscosity (10 °C 1.31 mPa·s, 20 °C 1.00) Pa·s
\(\rho\) Water density kg/m³
\(V\) Stage volume m³
\(L\) Side of a cubic stage m
\(T_e\) Equivalent tank diameter m
\(0.45T_e\) Suggested impeller diameter m
\(P\) Water power W
\(N\) Impeller speed rad/s
\(v_{tip}\) Tip speed m/s
\(Q_p\) Impeller pumping rate m³/s
\(t_c\) Circulation time s
\(Gt\) Gt for this stage -

Method and standards

Camp–Stein velocity gradient with the impeller power number relation.

Where it is used

  • Sizing flocculator drives and choosing speeds.
  • Checking existing flocculators against G and Gt guidance.

Common mistakes

  • Using the motor rating as water power (gearbox and motor losses are extra).
  • Using viscosity at 20 °C for a cold-water design.

Assumptions and limits

  • Fully turbulent impeller (constant power number); the cubic stage is a sizing assumption.

Questions and answers

What is G?

Camp and Stein's root-mean-square velocity gradient, G = √(P/μV); it measures how hard the water is stirred and so how often particles collide.

Why taper G through the stages?

Large flocs break up at high shear; tapering lets them grow while keeping enough collisions.

What do the defaults represent?

An illustrative case: Third stage of the same train at G 40. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 9-7, eqs. 9-40 and 9-63, Table 9-13 and Example 9-8

Related calculators