Worked example
Example: Reservoir 1.5 mg/L, 0.02 1/h at 20 C, Ea 70 kJ/mol, summer 30 C, 48 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Initial residual | 1.5000 mg/L |
| Decay constant at the test temperature | 0.020000 1/h |
| Test temperature | 20.000 °C |
| Activation energy | 70.000 kJ/mol |
| Other temperature | 30.000 °C |
| Storage or travel time | 48.000 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Decay constant at the other temperature | 0.051578 1/h |
| Residual after the time at T₁ | 0.57434 mg/L |
| Residual after the time at T₂ | 0.12615 mg/L |
| Half-life at T₁ | 34.657 h |
| Half-life at T₂ | 13.439 h |
Open this example in the calculator and change any input.
Formula
\(C = C_0e^{-k_dt}, \quad k_{d,2} = k_{d,1}\exp\left[\frac{E_a}{R}\left(\frac{1}{T_1} - \frac{1}{T_2}\right)\right], \quad t_{1/2} = \frac{\ln 2}{k_d}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_0\) | Initial residual | kg/m³ |
| \(k_{d,1}\) | Decay constant at the test temperature | 1/s |
| \(T_1\) | Test temperature | K |
| \(E_a\) | Activation energy | J/mol |
| \(T_2\) | Other temperature | K |
| \(t\) | Storage or travel time | s |
| \(k_{d,2}\) | Decay constant at the other temperature | 1/s |
| \(C_1(t)\) | Residual after the time at T₁ | kg/m³ |
| \(C_2(t)\) | Residual after the time at T₂ | kg/m³ |
| \(t_{1/2,1}\) | Half-life at T₁ | s |
| \(t_{1/2,2}\) | Half-life at T₂ | s |
Method and standards
First-order decay with Arrhenius temperature dependence.
Where it is used
- Booster chlorination planning and storage tank residuals.
- Seasonal dosing adjustments.
Common mistakes
- Using °C in the Arrhenius equation.
- Assuming bulk decay covers wall demand in old mains.
Assumptions and limits
- First-order bulk decay; constant temperature during the time.
Questions and answers
Why does warm water lose chlorine faster?
The decay reactions follow Arrhenius kinetics; with E_a about 60 kJ/mol the rate nearly quadruples from 10 to 25 °C.
How do I get k_d?
Dose a sample, store it dark at constant temperature and measure the residual; the slope of ln(C/C₀) against time is −k_d.
What do the defaults represent?
An illustrative case: Reservoir 1.5 mg/L, 0.02 1/h at 20 C, Ea 70 kJ/mol, summer 30 C, 48 h. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 13-5, Example 13-5, with the Arrhenius equation 5-85