Worked example
Example: Small plant 2,000 m3/d, 20 min in 300 m of pipe; old basin L/W 6, Ci 7.1. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flow | 2,000.0 m³/d |
| Hydraulic residence time | 20.000 min |
| Pipeline length | 300.00 m |
| Darcy friction factor of the pipeline | 0.022000 - |
| Serpentine basin length-to-width ratio (flow path) | 6.0000 - |
| Coefficient of ideality (3 good design, 7.1 typical older basin) | 7.1000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pipeline diameter for the residence time | 343.35 mm |
| Pipeline velocity | 0.25000 m/s |
| Dispersion number, Taylor 5.05(D/L)(f/8)^½ | 3.0310e-04 |
| Dispersion number, Sjenitzer 89,500 f^3.6 (D/L)^0.859 | 2.8701e-04 |
| Serpentine basin dispersion number 0.14 C_i/(L/W) | 0.16567 |
| Basin baffling factor 0.198 ln(L/W) − 0.002 | 35.277 % |
Open this example in the calculator and change any input.
Formula
\(D = \sqrt{\frac{4Q\tau}{\pi L}}, \quad d_{Taylor} = 5.05\frac{D}{L}\sqrt{\frac{f}{8}}, \quad d_{Sjenitzer} = 89\,500f^{3.6}\left(\frac{D}{L}\right)^{0.859}\)
\(d_{basin} = \frac{0.14C_i}{L/W}, \quad \frac{t_{10}}{\tau} = 0.198\ln\left(\frac{L}{W}\right) - 0.002\)
Variables
| Symbol | Meaning | SI unit | |
|---|---|---|---|
| \(Q\) | Flow | m³/s | |
| \(\tau\) | Hydraulic residence time | s | |
| \(L\) | Pipeline length | m | |
| \(f\) | Darcy friction factor of the pipeline | - | |
| \(L/W\) | Serpentine basin length-to-width ratio (flow path) | - | |
| \(C_i\) | Coefficient of ideality (3 good design, 7.1 typical older basin) | - | |
| \(D\) | Pipeline diameter for the residence time | m | |
| \(v\) | Pipeline velocity | m/s | |
| \(d_{Taylor}\) | Dispersion number, Taylor 5.05(D/L)(f/8)½ | - | |
| \(d_{Sjenitzer}\) | Dispersion number, Sjenitzer 89,500 f3.6 (D/L)^0.859 | - | |
| \(d_{basin}\) | Serpentine basin dispersion number 0.14 C_i/(L/W) | - | |
| \(t_{10}/\tau\) | Basin baffling factor 0.198 ln(L/W) − 0.002 | - |
Method and standards
Axial dispersion correlations for pipes and baffled channels used as disinfection contactors.
Where it is used
- Sizing chlorine and chloramine contactors.
- Choosing the number of baffles in a clearwell.
Common mistakes
- Using a nominal pipe size without rechecking τ.
- Expecting real basins to reach the ideal 0.14/(L/W).
Assumptions and limits
- Long straight pipelines; baffled rectangular basins with H/W of 1 to 3.
Questions and answers
Why is a long pipeline such a good contactor?
Its dispersion number is tiny, so it behaves almost as ideal plug flow and earns full CT credit.
How do baffles help a tank?
They lengthen the flow path; dispersion falls in proportion to 1/(L/W) and t₁₀/τ rises with ln(L/W).
What do the defaults represent?
An illustrative case: Small plant 2,000 m3/d, 20 min in 300 m of pipe; old basin L/W 6, Ci 7.1. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 13-8, eqs. 13-42 to 13-53 and Example 13-10 (Taylor 1954; Sjenitzer 1958; Trussell and Chao 1977; Ducoste et al. 2001)