Disinfection Contactor Dispersion: Pipeline and Serpentine Basin

Pipeline contactor diameter and dispersion number (Taylor and Sjenitzer) and serpentine basin dispersion and t10/τ from the length-to-width ratio.

Inputs

Examples: Small plant 2,000 m3/d, 20 min in 300 m of pipe; old basin L/W 6, Ci 7.1Large plant 200 ML/d, 45 min in 3 km; well-baffled basin L/W 100

Accepted: 8.64 to 4,320,000 m³/d
Accepted: 0.16667 to 600 min
Accepted: 1 to 100,000 m
Accepted: 0.005 to 0.1
Accepted: 1 to 500
Accepted: 1 to 20

Results

Sjenitzer's field correlation fits measured pipeline dispersion better than Taylor's theory; both assume a long straight pipe. A dispersion number below about 0.006 keeps 4-log inactivation within 5 % of plug flow.

Pipeline diameter for the residence time343.35mm
Pipeline velocity0.25000m/s
Dispersion number, Taylor 5.05(D/L)(f/8)^½3.0310e-04
Dispersion number, Sjenitzer 89,500 f^3.6 (D/L)^0.8592.8701e-04
Serpentine basin dispersion number 0.14 C_i/(L/W)0.16567
Basin baffling factor 0.198 ln(L/W) − 0.00235.277%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Small plant 2,000 m3/d, 20 min in 300 m of pipe; old basin L/W 6, Ci 7.1. The inputs, in the units selected above:

InputValue
Flow2,000.0 m³/d
Hydraulic residence time20.000 min
Pipeline length300.00 m
Darcy friction factor of the pipeline0.022000 -
Serpentine basin length-to-width ratio (flow path)6.0000 -
Coefficient of ideality (3 good design, 7.1 typical older basin)7.1000 -

Applying the formula below gives:

ResultValue
Pipeline diameter for the residence time343.35 mm
Pipeline velocity0.25000 m/s
Dispersion number, Taylor 5.05(D/L)(f/8)^½3.0310e-04
Dispersion number, Sjenitzer 89,500 f^3.6 (D/L)^0.8592.8701e-04
Serpentine basin dispersion number 0.14 C_i/(L/W)0.16567
Basin baffling factor 0.198 ln(L/W) − 0.00235.277 %

Open this example in the calculator and change any input.

Formula

\(D = \sqrt{\frac{4Q\tau}{\pi L}}, \quad d_{Taylor} = 5.05\frac{D}{L}\sqrt{\frac{f}{8}}, \quad d_{Sjenitzer} = 89\,500f^{3.6}\left(\frac{D}{L}\right)^{0.859}\)

\(d_{basin} = \frac{0.14C_i}{L/W}, \quad \frac{t_{10}}{\tau} = 0.198\ln\left(\frac{L}{W}\right) - 0.002\)

Variables

Symbol Meaning SI unit
\(Q\) Flow m³/s
\(\tau\) Hydraulic residence time s
\(L\) Pipeline length m
\(f\) Darcy friction factor of the pipeline -
\(L/W\) Serpentine basin length-to-width ratio (flow path) -
\(C_i\) Coefficient of ideality (3 good design, 7.1 typical older basin) -
\(D\) Pipeline diameter for the residence time m
\(v\) Pipeline velocity m/s
\(d_{Taylor}\) Dispersion number, Taylor 5.05(D/L)(f/8)½ -
\(d_{Sjenitzer}\) Dispersion number, Sjenitzer 89,500 f3.6 (D/L)^0.859 -
\(d_{basin}\) Serpentine basin dispersion number 0.14 C_i/(L/W) -
\(t_{10}/\tau\) Basin baffling factor 0.198 ln(L/W) − 0.002 -

Method and standards

Axial dispersion correlations for pipes and baffled channels used as disinfection contactors.

Where it is used

  • Sizing chlorine and chloramine contactors.
  • Choosing the number of baffles in a clearwell.

Common mistakes

  • Using a nominal pipe size without rechecking τ.
  • Expecting real basins to reach the ideal 0.14/(L/W).

Assumptions and limits

  • Long straight pipelines; baffled rectangular basins with H/W of 1 to 3.

Questions and answers

Why is a long pipeline such a good contactor?

Its dispersion number is tiny, so it behaves almost as ideal plug flow and earns full CT credit.

How do baffles help a tank?

They lengthen the flow path; dispersion falls in proportion to 1/(L/W) and t₁₀/τ rises with ln(L/W).

What do the defaults represent?

An illustrative case: Small plant 2,000 m3/d, 20 min in 300 m of pipe; old basin L/W 6, Ci 7.1. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 13-8, eqs. 13-42 to 13-53 and Example 13-10 (Taylor 1954; Sjenitzer 1958; Trussell and Chao 1977; Ducoste et al. 2001)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.